Download Print this page

External Connections - Omron E5GCCX2D6M000 Manual

Digital temperature controller

Advertisement

E5DC/E5DC-B

External Connections

E5DC (Models with Screw Terminal Blocks)
Control output
Relay outputs
Relay output
250 VAC, 3 A (resistive load)
Voltage output (for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 : max.
(3) Input Power Supply
(6) Options
002
Communications and 1 CT
RS-485
015
Communications
RS-485
016
One event input
017
One event input and 1 CT
Use no-voltage inputs for the event inputs.
The polarity for non-contact inputs is given in parentheses.
Note: 1. The application of the terminals depends on the model.
2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30m,
compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.
5. Due to UL Listing requirements, use the E54-CT1L or E54-CT3L Current Transformer with the factory wiring (internal wiring).
Use a UL category XOBA or XOBA7 current transformer that is UL Listed for field wiring (external wiring) and not the factory wiring
(internal wiring).
6. The terminal layout is different than models with Push-In Plus terminal blocks. Check the terminal arrangement before wiring.
68
Auxiliary outputs 1, 2
250 VAC: 2 A (resistive load)
24 VAC/DC
100 to 240 VAC
1
1
2
2
(no polarity)
B(+)
3
7
CT1
4
8
A(-)
B(+)
7
3
8
4
A(-)
(-)
3
7
4
8
EV1
(-)
7
3
CT1
8
4
EV1
The E5DC is set for a K-type thermocouple (input type = 5) by default.
An input error (s.err) will occur if the input type setting does not agree
with the temperature sensor. Check the input type.
E5DC
S
M
(1)
(2)(3)(4)(5)
Terminal type
(1) Control Output
RX
QX
1 relay
1 voltage output
output
(for driving SSR)
5
5
R
6
6
1
5
9
2
6
10
(2) Auxiliary Outputs
9
11
Auxiliary output 2
10
Auxiliary output 1
11
* When connecting different potentials to
auxiliary outputs 1 and 2, check the
single fault condition of the common
terminal before use.
12
(5) Sensor (Temperature/Analog) Input
TC
3
7
13
12
-
4
8
14
13
14
+
(6)
CX
1 linear
current output
5
+
+
Q
C
-
-
6
Pt
I
V
A
+
12
12
12
B
mA
-
13
13
13
-
B
V
14
14
14
+

Advertisement