External Connections

• A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit
Controllers
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Control outputs 1, 2
Output Unit
Control outputs 1, 2
Relay Outputs
250 VAC, 5 A
(resistive load)
SSR Outputs
75 to 250 VAC, 1A
(resistive load)
Models with Position-
proportional Control
250 VAC, 1 A
(including inrush
current)
Auxiliary outputs 1, 2
Relay output
SPST-NO,
250 VAC, 3 A
(resistive load)
A heater burnout alarm, SSR
failure, heater overcurrent
alarm, or input alarm is sent
to the output to which the
alarm 1 function is assigned.
Note: Wire all voltage input terminals correctly. The Controller may fail if voltage input terminals are wired incorrectly.
Downloaded from
Elcodis.com
electronic components distributor
1
21
21
11
Input power
supply
2
22
22
12
3
23
23
13
Control output 1
4
24
24
14
5
25
25
15
Control output 2
6
26
26
16
7
27
27
17
Auxiliary output 2
8
28
28
18
9
29
29
19
Auxiliary output 1
10
30
30
20
21
22
23
EV3
24
EV4
25
DON'T USE
26
27
4 to 20 mA DC
Transfer output
(Load: 600 Ω max.)
28
29
4 to 20 mA DC
Remote SP input
30
Advanced Digital Temperature Controller

Option Units

Communications
E53-EN01
E53-EN02
RS-232C
RS-422
11
11
SD
RDB
12
RD
12
RDA
13
SG
13
SG
21
DO NOT USE
21
SDB
22
22
SDA
DO NOT USE
Potentiometer
CT2
O
14
CT1
W
15
Auxiliary output 3
CT2
16
C
DON'T
DON'T
USE
USE
A
DON'T
DON'T
V
USE
USE
B
DON'T
B
USE
mA
V
t/c
E53-EN03
E53-AKB
RS-485
Event Inputs
11
11
B (+)
EV2
12
A (−)
12
13
DO NOT USE
13
21
B (+)
21
22
A (−)
22
Auxiliary output 3
Relay output
SPDT, 250 VAC, 3 A
(resistive load)
DON'T
USE
mA
DON'T
USE
Pt
E5AN-H/E5EN-H