External Connections - Omron E5DC Manual

Digital temperature controller
Hide thumbs Also See for E5DC:
Table of Contents

Advertisement

External Connections

E5DC
Control output
Auxiliary outputs 1, 2
Relay outputs
Relay output
250 VAC: 2 A (resistive load)
250 VAC, 3 A (resistive load)
Voltage output (for driving SSR)
12 VDC, 21 mA
Linear current output
0 to 20 mA DC
4 to 20 mA DC
Load: 500 Ω max.
Input Power Supply
100 to 240 VAC
Options
002
Communications and 1 CT
B(+)
RS-485
A(-)
015
Communications
B(+)
RS-485
A(-)
016
One event input
(-)
EV1
017
One event input and 1 CT
(-)
EV1
Use no-voltage inputs for the event inputs.
The polarity for non-contact inputs is given in parentheses.
Note: 1. The application of the terminals depends on the model.
2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30m,
compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.
5. Due to UL Listing requirements, use the E54-CT1L or E54-CT3L Current Transformer with the factory wiring (internal wiring).
Use a UL category XOBA or XOBA7 current transformer that is UL Listed for field wiring (external wiring) and not the factory wiring
(internal wiring).
Isolation/Insulation Block Diagrams
Sensor input and CT input
Communications and event input
Power
Voltage output (for driving SSR) and linear current output
supply
Auxiliary outputs 1 and 2
: Reinforced insulation
: Functional isolation
Note: Auxiliary outputs 1 to 2 are not insulated.
The E5DC is set for a K-type thermocouple (input type = 5) by default.
An input error (s.err) will occur if the input type setting does not agree
with the temperature sensor. Check the input type.
24 VAC/DC
1
1
2
2
(no polarity)
1
2
3
7
CT1
4
8
7
3
8
4
3
4
3
7
4
8
7
3
CT1
8
4
Relay output
E5DC
M
Control output
Options
Control Output
RX
QX
1 relay
1 voltage output
(for driving SSR)
output
5
5
+
Q
R
-
6
6
5
9
6
10
Auxiliary Outputs
9
11
Auxiliary output 2
10
Auxiliary output 1
11
Sensor (Temperature/Analog) Input
TC
Pt
A
12
12
12
-
B
13
13
B
7
13
14
14
+
8
14
E5DC
CX
1 linear
current output
5
+
C
-
6
I
V
+
12
12
mA
-
13
13
-
V
14
14
+
67