External Connections - Omron E5CWL Connections

Hide thumbs Also See for E5CWL:
Table of Contents

Advertisement

External Connections

 A voltage output (control output) is not electrically insulated from the internal circuits. When using a grounding thermocouple, do not connect
any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the measured
temperature values as a result of leakage current.
E5CSL
Control Output
• Relay output: 250 VAC, 3 A (resistive load)
• Voltage output (for driving SSR): 12 VDC, 21 mA
A
B
B
Pt input
E5CWL
Control Output
• Relay output: 250 VAC, 3 A (resistive load)
• Voltage output (for driving SSR): 12 VDC, 21 mA
A
B
B
Pt input
Nomenclature
E5CSL
(3)
(7)
(4)
(9)
(8)
E5CWL
(5)
(6)
(7)
(9)
(8)
(1) Display No. 1
Displays the process value (PV) or parameter. For the E5CSL/E5EWL,
the set point or parameter setting is also displayed.
(2) Display No. 2
Displays the set point (SP) or parameter setting.
(3) Deviation
Show the relation between the process value and the set point.
Indicators
Lit: The process value is more than 5°C/°F higher than the set point.
Lit: The process value is more than 5°C/°F lower than the set point.
Lit: The process value is within 5°C/°F of the set point.
The relevant deviation indicator will flash during autotuning.
(4) SP
Lit while the set point is displayed on display No. 1 (E5CSL only).
(5) ALM
Lit while the alarm is ON. Not lit while the alarm is OFF.
(6) OUT
Lit while the control output is ON. Not lit while the control output is
OFF.
(7) STOP
Not lit during operation. Lit while operation is stopped.
(8) O
Level Key: Changes the setting level.
(9) M
Mode Key: Changes the parameter within the setting level.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
+
1
Control output
2
3
DO NOT
USE
4
9
+
5
10
TC input
+
1
Control output
2
7
Alarm Output
3
8
DO NOT
Relay output: 250 VAC, 1 A
USE
4
9
+
5
10
TC input
(12)
(13)
(14)
(12)
(13)
(14)
E5EWL
Input power supply:
100 to 240 VAC,
50/60 Hz
(resistive load)
Input power supply:
100 to 240 VAC,
50/60 Hz
E5EWL
(1)
(6)
(10)
(11)
(7)
(6)
(1)
(9)
(2)
(8)
(10)
(12)
(13)
(11)
(10) D
Down Key: Reduces the setting.
(11) U
Up Key: Increases the setting.
(12) O+M
Press these keys for at least 3 seconds in Operation Level or Adjustment Level to go to Protect Level.
Press these keys for at least 1 second in Protect Level to return to Operation Level.
(13) M+D
Press these keys for at least 2 seconds to start or stop autotuning.*1
(14) M+U
Press these keys for at least 2 seconds to start or stop operation.*2
*1: These keys are disabled when starting and stopping autotuning has been disabled with operation control
key protection.
*2: These keys are disabled when starting and stopping operation has been disabled with operation control
key protection.
E5CSL/E5CWL/E5EWL
Control Output
• Relay output: 250 VAC, 3 A (resistive load)
• Voltage output (for driving SSR): 12 VDC, 21 mA
1
6
Input power supply:
100 to 240 VAC,
50/60 Hz
2
7
8
• Relay output: 250 VAC, 1 A
3
(resistive load)
4
9
Alarm Output
10
(1)
(2)
(5)
(10)
(11)
(14)
Control output
A
DO NOT USE
B
B
TC input
Pt input
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents