Proof Test (Whg, Sil) - KROHNE OPTISWITCH 5300 Handbook

Vibrating level switch
Hide thumbs Also See for OPTISWITCH 5300:
Table of Contents

Advertisement

6 Setup
Mode on the
Level
signal con-
ditioning
instrument
Mode max.
Overflow pro-
tection
Mode max.
Overflow pro-
tection
Mode min.
Dry run pro-
tection
Mode min.
Dry run pro-
tection
Failure of the
any
supply volt-
age
Mode (max./
min.)
Fault message
any
Mode (max./
min.)
Implementation - Func-
tion test
24
Note:
Keep in mind that the mode switch of OPTISWITCH 5300 C must be
always set to "max.".
Sensor
Signal cur-
Signal lamp -
rent - Sensor
green
Voltage sup-
ply
approx. 8 mA
approx. 16 mA
approx. 16 mA
approx. 8 mA
-
approx.
3.6 mA
6.4

Proof test (WHG, SIL)

To find out possible undetected, dangerous failures, a proof test must
be carried out in adequate time intervals to check the safety function.
It is the user's responsibility to choose the type of testing.
You will find further instructions in the Safety Manual.
The following options are available for carrying out the proof test
(WHG, SIL):
Electronics directly evaluated via the analogue input of a control system
1)
(without signal conditioning instrument)
Signal lamp -
Signal lamp
yellow
- red
Switching
Fault mes-
status
sage
OPTISWITCH 5300 C • - two-wire
Signal con-
ditioning
instrument
Analogue
- input con-
trol
1)
> 3.8 mA
< 11.5 mA
> 12.5 mA
< 21.6 mA
> 12.5 mA
< 21.6 mA
> 3.8 mA
< 11.5 mA
≤ 3.6 mA
≥ 21 mA
≤ 3.6 mA
≥ 21 mA