Supply Through Ossd - Bosch Rexroth IndraControl S20-PSDI-8/4 Application Description

With safe digital inputs
Table of Contents

Advertisement

44/102
Bosch Rexroth AG
Connection examples for safe inputs
Parameterization
Input xx channel 1/channel 2
Assignment
Filter time (t
)
Filter
Symmetry
Start inhibit due to symmetry viola-
tion
Cross-circuit monitoring
8.3.4

Supply through OSSD

Sensor
Sensor supply
Achievable SIL/SILCL/Cat./PL
DBR Automation is Bosch Rexroth Oficial Sales Partner. Interested in products or technical support? www.dbrautomation.com | +34951709474 | comercial@dbrautomation.com
IndraControl S20 Module With Safe Digital Inputs S20-PSDI-8/4
Typical parameterization
Parameterized as/value range
Both single-channel
3 ms
Disabled
Disabled
No cross-circuit monitoring
OSSD
+24 V
IN1_Ch1
GND
Fig. 8-7
Single-channel assignment of inputs: external supply (OSSD)
WARNING
Parasitic voltages can result in the loss of the safety function.
Connect the sensor ground directly to terminal point GND of the module. An
external ground may not be used.
Basic specifications
Single-channel OSSD output (with internal testing)
External (OSSD sensor)
SIL 2/SILCL 2/Cat. 2/PL d
DANGER
Cross-circuits can result in the loss of the safety function.
Prevent cross-circuits to achieve the specified PL.
DOK-CONTRL-S20*PSDI*8*-AP02-EN-P
Remark
Application-specific
70070027
Loss of safety function
Loss of safety function