Examples For Reading A Diagnostic Message - Bosch Rexroth IndraControl S20-PSDI-8/4 Application Description

With safe digital inputs
Table of Contents

Advertisement

DOK-CONTRL-S20*PSDI*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Inputs S20-PSDI-8/4
10.1.5

Examples for reading a diagnostic message

DBR Automation is Bosch Rexroth Oficial Sales Partner. Interested in products or technical support? www.dbrautomation.com | +34951709474 | comercial@dbrautomation.com
Reading an error due to cross-circuit at channel 3 (priority 2) with
Example 1:
subsequent acknowledgment
Read DiagState object 0x0018
DiagState of slot 1:
Lfd.Nr.:
Priority:
Channel/
Group/Module:
Code:
MoreFollows:
Text:
Read DiagStateChannelNo object 0x0033
Lfd.Nr.:
ChannelNo:
You can acknowledge the error after removing the error cause.
Write "05hex" to ResetDiag object 0x0019.
Reading a parameterization error (priority 1)
Example 2:
Read DiagState object 0x0018
DiagState of slot 1:
Lfd.Nr.:
Priority:
Channel/
Group/Module:
Code:
MoreFollows:
Text:
Read DiagStateChannelNo object 0x0033
Lfd.Nr.:
ChannelNo:
Read DiagStateAddValue object 0x0034
Lfd.Nr.:
AddValue:
This error cannot be acknowledged as it is a priority 1 error.
Check and correct the parameterization.
1
0x02 (2), warning active
3
0x2141 (8513), cross-circuit to another input or external voltage
02 DiagStateAddValue available
1
0x03
2
0x01 (1), alarm active
0
0x6320 (25376), parameter table invalid
02 DiagStateAddValue available
2
0x0000
2
0x0340
Bosch Rexroth AG
69/102
Errors: messages and removal

Advertisement

Table of Contents
loading

Table of Contents