Bosch Rexroth IndraControl S20-PSDI-8/4 Application Description page 81

With safe digital inputs
Table of Contents

Advertisement

DOK-CONTRL-S20*PSDI*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Inputs S20-PSDI-8/4
Safety characteristics according to EN ISO 13849-1
Achievable performance level
Diagnostic coverage (DC)
Mean time to dangerous failure (MTTFd)
Supply voltage U
The bus coupler or a feed-in terminal in the station supply the module with communications power U
For the technical data, please refer to the data sheet for the bus coupler or the feed-in terminal.
Communications power (logic voltage)
Current consumption from U
Supply voltage U
WARNING
The use of unsuitable power supplies can result in the loss of the safety function.
Use power supplies according to EN 50178/VDE 0160 (PELV).
Nominal voltage
Ripple
Permissible voltage range
Current consumption
Permissible interrupt time
Surge protection
Protection against polarity reversal
NOTICE
Parallel protection against polarity reversal is only implemented in the module for a limited period. The following measures
must be taken to prevent damage to the module:
Due to the maximum current capacity of 8 A, protect power supply U
Only use PELV power supply units with at least four times the nominal tripping current, as this is the only way to ensure
release times of less than 300 ms.
Undervoltage detection
Diagnostics indicators
External protection
DBR Automation is Bosch Rexroth Oficial Sales Partner. Interested in products or technical support? www.dbrautomation.com | +34951709474 | comercial@dbrautomation.com
(logic)
BUS
BUS
(sensors, clock outputs, I/O)
I
Loss of safety function
Module damage
Technical data and ordering data
PL d (single-channel)
PL e (two-channel)
Depends on the parameterization and wiring: see
tion options for sensors depending on the parameterization"
on page
16, see
"Connection examples for safe inputs" on
page
37.
99%
100 years (regardless of whether single-channel or two-chan-
nel operation)
5 V DC
280 mA, typical (all inputs set; supply by U
19.2 V DC ... 30.2 V DC)
310 mA, maximum
24 V DC according to EN 61131-2 and EN 60204
3.6 V
PP
19.2 V DC ... 30.2 V DC (including all tolerances, ripple in-
cluded)
9 mA, typical
(all inputs set; supply by U
with 30.2 V DC; without supply to
I
the sensors via clock supplies T1 and T2)
1 ms
(output voltage of the clock outputs can fail)
Yes
Parallel protection against polarity reversal for a limited period
externally with an 8 AT fuse.
I
At 16.6 V
Green U
LED:
I
See
"Local diagnostics and status indicators" on page
8 A slow-blow, maximum
Bosch Rexroth AG
79/102
"Connec-
.
BUS
of
I
17.