Diagstate Object 0X0018 - Bosch Rexroth IndraControl S20-PSDI-8/4 Application Description

With safe digital inputs
Table of Contents

Advertisement

DOK-CONTRL-S20*PSDI*8*-AP02-EN-P
IndraControl S20 Module With Safe Digital Inputs S20-PSDI-8/4
10.1.1

DiagState object 0x0018

Index
Object name Object
0x0018 DiagState
.1 Lfd.Nr.
.2 Priority
.3 Channel/
Group/
Module
.4 Code
.5 MoreFollows
.6 Text
DBR Automation is Bosch Rexroth Oficial Sales Partner. Interested in products or technical support? www.dbrautomation.com | +34951709474 | comercial@dbrautomation.com
The diagnostic object DiagState 0x0018 has the following structure:
Data type
N L [bytes] Rights
type
Record
6
Var
Unsigned 16
1 2
Var
Unsigned 8
1 1
Var
Unsigned 8
1 1
Var
Octet string
1 2
Var
Bit string 8
1 1
Var
Visible string 1 Max.
Fig. 10-5
DagState object
Meaning
R
Diagnostic state
R
Consecutive error number since the last reset or
error memory reset
R
Priority of the message:
1: highest priority, error that cannot be acknowl-
edged
2: error that can be acknowledged
R
Channel, group or module where the error oc-
curred
FF: entire device
R
Error code (see
R
Additional error information:
00 - channel number that can be read via Diag-
StateChannelNo.
(see
"DiagStateChannelNo object 0x0033" on
page
68)
01 - additional information that can be read via
the DiagStateLong object
02 - AddValue that can be read via DiagStateAd-
dValue
(see
"DiagStateAddValue object 0x0034" on
page
68)
04 - a group is affected
08 - a module is affected
R
Plain text message. Default: status OK
50 + 1
Bosch Rexroth AG
67/102
Errors: messages and removal
"Error codes" on page
70)

Advertisement

Table of Contents
loading

Table of Contents