Table 6.4 Backup Time for 8kVA/8kW VRLA Models in Minutes
Number of Battery
Setting
1
2
3
4
5
Table 6.5 Backup Time for 10kVA/10kW VRLA Models in Minutes
Number of Battery
Setting
1
2
3
4
5
Table 6.6 Backup Time for 5kVA/5kW 1U Lithium Models in Minutes
Number of Battery
Settings
1
2
3
4
5
6
7
8
6 Specifications
100%
90%
80%
8 kW
7.2 kW
6.4 kW
13
15
18
33
36
40
52
61
71
76
91
103
103
112
130
100%
90%
80%
10 kW
9 kW
8 kW
8
9
11
21
25
28
35
38
46
49
55
67
67
76
91
100%
90%
80%
5 kW
4.5 kW
4 kW
20
24
28
44
50
56
68
76
86
92
102
116
116
128
146
142
156
178
166
184
206
188
210
234
Proprietary and Confidential ©2024 Vertiv Group Corp.
Load Level
70%
60%
50%
5.6 kW
4.8 kW
4 kW
21
26
33
49
61
76
82
103
126
121
137
152
143
156
181
Load Level
70%
60%
50%
7 kW
6 kW
5 kW
13
16
21
34
39
49
53
67
82
78
98
121
105
126
143
Load Level
70%
60%
50%
3.5 kW
3 kW
2.5 kW
32
38
44
64
76
90
100
116
140
134
156
188
168
196
234
202
238
284
234
278
330
270
316
376
Vertiv™ Liebert® ITA2 Installer/User Guide
40%
30%
20%
3.2 kW
2.4 kW
1.6 kW
40
56
101
102
135
167
147
167
314
181
227
347
219
318
540
40%
30%
20%
4 kW
3 kW
2 kW
28
39
66
67
98
142
109
143
193
143
165
310
161
212
337
40%
30%
20%
2 kW
1.5 kW
1 kW
56
74
106
114
148
222
172
224
332
230
298
438
290
376
550
350
450
664
408
530
776
468
610
890
10%
0.8 kW
166
345
650
870
1000
10%
1 kW
142
309
480
620
770
10%
0.5 kW
192
420
636
852
1074
1280
1500