Liebert® ITA2
Installer/User Guide
5 - 10kVA, 60Hz, 208/220V, Three-Phase UPS

Advertisement

Table of Contents
loading

Summary of Contents for Vertiv Liebert ITA2

  • Page 1 Liebert® ITA2 Installer/User Guide 5 - 10kVA, 60Hz, 208/220V, Three-Phase UPS...
  • Page 2 The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
  • Page 3: Table Of Contents

    2.8.2 REPO Connection 2.8.3 Dry Contact Connections 2.8.4 Connecting USB Communication Cables 2.9 Connecting Serial Port Communication Cables 2.9.1 Connecting Multi-Function Port (RJ-45) 3 Operation and Display Panel 3.1 LED Indicators 3.2 Audible Alarm (Buzzer) Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 4 4.7 Remote Emergency Power Off (REPO) 5 Maintenance 5.1 Cleaning the UPS 5.2 Routine Maintenance 6 Specifications 6.1 Standard Battery Backup Time with a Single UPS Appendices Appendix A: UPS Prompts and Alarms Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 5: Important Safety Information

    IMPORTANT! This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries. Read this manual thoroughly and the safety and regulatory information, available at https://www.vertiv.com/ComplianceRegulatoryInfo, before attempting to install, connect to supply, or operate this UPS.
  • Page 6 Vertiv™ Liebert® ITA2 Installer/User Guide This page intentionally left blank Important Safety Information Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 7: Product Description

    Vertiv™ Liebert® ITA2 Installer/User Guide 1 Product Description The Vertiv™ Liebert® ITA2 uninterruptible power system (UPS) is an intelligent, online UPS with sine wave output. The UPS offers reliable, high-quality AC power to small-scale computer centers, networks, communication systems, automatic control systems, and similar sensitive electronic equipment.
  • Page 8: Rear Panel Components

    Vertiv™ Liebert® IntelliSlot™ port Dry contact port REPO port RS-232 port Multi-function port Parallel/LBS ports Ventilation holes AC output terminals AC input terminals Ventilation holes Battery input terminals USB port 1 Product Description Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 9: Ups States And Operating Modes

    Battery-connector ports USB port 1.3 UPS States and Operating Modes NOTE: See Table 3.2 on page 44 , for description of the run indicator and alarm indicator LED's mentioned in this section. 1 Product Description Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 10: Normal Mode

    Normal operation supplies clean, conditioned, sine wave power to connected equipment from normal utility input. The battery charger charges the batteries. On the front panel display, the run indicator (green) is On, the alarm indicator is Off and the buzzer is silent. Figure 1.4 Normal Mode Operation 1 Product Description Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 11: Battery Mode

    Bypass input Maintenance bypass breaker (MBB) Bypass input breaker (BIB) Static switch Rectifier input Rectifier input breaker (RIB) Rectifier Battery charger Battery Inverter Automatic inverter switch Maintenance isolation breaker (MIB) UPS output 1 Product Description Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 12: Bypass Mode

    Bypass input Maintenance byass breaker (MBB) Bypass input breaker (BIB) Static switch Rectifier input Rectifier input breaker (RIB) Rectifier Battery charger Battery Inverter Automatic inverter switch Maintenance isolation breaker (MIB) UPS output 1 Product Description Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 13: Auto Restart Mode

    UPS components. The optional Liebert® ITA2 Maintenance Bypass Cabinet (MBC) is required for this mode. If your system includes a Liebert ITA2 MBC, refer to the Liebert ITA2 MBC Installer/User Guide available on the product page at www.Vertiv.com. NOTICE Risk of power interruption.
  • Page 14 Vertiv™ Liebert® ITA2 Installer/User Guide This page intentionally left blank 1 Product Description Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 15: Installation

    Be clean and well-ventilated. • Be free from water, heat source and flammable and explosive substances. • Be free from dust, volatile gases and corrosive materials. • Comply with local fire codes. 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 16: Installation Clearances

    IMPORTANT! All tools used to install and maintain the Liebert® ITA2 UPS and equipment must be insulated. The following tools are required to properly install your UPS: • Torque Wrench • Slotted screwdriver • Multimeter • #3 Phillips-head screwdriver • T10 Torx screwdriver 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 17: Storage

    The residual current circuit breaker (RCCB) must be sensitive to the DC unidirectional pulse (Level A) in the power distribution network, but insensitive to the transient current pulse, see Figure 2.2 below . Figure 2.2 RCCB Symbols 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 18: Equipment Handling And Unpacking

    When using the earth RCD in a split-bypass system, the RCD should be installed at the upstream input power distribution end to prevent false alarms. The earth leakage current fed by the RFI filter in the UPS ranges from 3.5 mA to 100 mA. Vertiv recommends that you verify the sensitivity of each differential device of the upstream input power distribution and downstream power distribution (to load).
  • Page 19 5. Place the UPS, battery cabinets and the MBC on the two support base assemblies. Figure 2.3 Support Bases Item Description Support bases Spacers with connectors Figure 2.4 Tower-Mounted Liebert® ITA2 UPS System with Battery Cabinets and MBC 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 20: Rack Installation

    Risk of improper installation can make the rack top-heavy and cause a tipping hazard. The battery cabinets are heavier than the UPS. Vertiv recommends installing the battery cabinets as close to the bottom of the rack as possible to maintain a low center of gravity. Install the UPS above the battery cabinets.
  • Page 21 Figure 2.5 Guide Rail and Rack Bracket Installation Item Description Bracket screw, four per bracket Bracket, two Rail screw, four per rail Guide rail, one per side Rack-mount screw, four per bracket 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 22: Connecting Power Cables

    Vertiv™ Liebert® ITA2 Installer/User Guide Figure 2.6 Rack-Mounted Vertiv™ Liebert® ITA2 UPS System with Battery Cabinets and MBC 2.5 Connecting Power Cables WARNING! Risk of electrical shock. Can cause property damage, injury and death. The unit has several circuits that are energized with high DC and AC voltages. Check for voltage with both AC and DC voltmeters before making contact and before working within the UPS.
  • Page 23: Connecting A Single-Input Configuration

    2. In addition, the input terminal leads to the interface with L21-20P, and the output terminal leads to the interface of L21-20R. Directly use the corresponding interface to plug in and connect to the external power supply. 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 24 5. Torque all customer-side connections per recommendations in Table 2.1 on the previous page , and Table 2.2 on the previous page 6. Replace the conduit box cover and secure it. 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 25 Vertiv™ Liebert® ITA2 Installer/User Guide Figure 2.7 Single- and Dual-Input Configuration Wiring Diagram (5kVA) Item Description Input L21-20P Output L21-20R Figure 2.8 Sinle-Input and Dual-Input Configuration Wiring Diagram (8kVA and 10kVA) 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 26: Connecting A Dual-Input Configuration

    Prepare for connection by removing the conduit box cover, opening knockout holes and routing cables through the conduit. 2. Remove the shorting busbars from the terminals labeled L1, L2, and L3 in Figure 2.7 on the previous page . 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 27: Connecting A Single Battery Cabinet System

    6. Torque all customer-side connections per recommendations in Table 2.1 on page 19 , and Table 2.2 on page 19 7. Replace the conduit box cover and secure it. 2.6 Connecting a Single Battery Cabinet System Do not reverse the polarity of the battery cables. 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 28: Connecting The Cables

    The battery-to-battery power cable connects additional battery strings/cabinets, see Connecting Additional Battery Cabinet Systems on page 33 . Figure 2.9 Power Cables Item Description UPS-to-battery cable (for hard-wired configurations) Battery-to-battery cable (also UPS-to-battery for plug-and-play configurations) 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 29 Connect the end labeled "Port B" to one of the connectors on the rear of the UPS and tighten the securing screws. • Connect the end labeled "Port A" to Connector A on the battery cabinet. 3. Repeat Step  2 , for the second battery cabinet. 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 30 5. For a single battery string, close the battery output breaker(s). – or – If you are installing additional battery strings (two battery cabinets each), proceed to Connecting Additional Battery Cabinet Systems on page 33 . 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 31 Ground screw (PE) BAT – (negative) connector BAT N (neutral) connector BAT + (positive) connector Communication port connector (RJ-45) Connector A Communication port Connector 1 Communication port Connector 2 Connector B 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 32 Communication cable, Comm Port 2 to Comm Port 1 on Battery Cabinet 3 Battery-to-battery power cable, Battery Cabinet 1 Connector B to Connector A on Battery Cabinet 3 Battery-to-battery power cable, Battery Cabinet 2 Connector B to Connector A on Battery Cabinet 4 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 33 Multi-function connector (RJ-45) Communication port connector (RJ-45) Communication port connector (RJ-45) Connector B Connector A DIP switch Battery Cabinet 4 Battery Cabinet 3 Battery String 2 Battery Cabinet 2 Battery Cabinet 1 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 34 Battery cable from Connector B on Battery Cabinet 1 to Connector A on Battery Cabinet 3 Battery cable from Connector B on Battery Cabinet 2 to Connector A on Battery Cabinet 4 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 35 Battery cable from Connector B on Battery Cabinet 2 or 4 to Connector A on Battery Cabinet 4 or 6 Communication cable between communication ports on each battery cabinet Communication cable between CANBus ports on each battery cabinet. DIP Switch (Address) Breaker 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 36 Vertiv™ Liebert® ITA2 Installer/User Guide Figure 2.14 Cabling 2U Lithium Battery in Parallel 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 37: Connecting Additional Battery Cabinet Systems

    UPS. For 2U battery cabinets, you must adjust the DIP switch on the rear panel for each cabinet in the string. To connect power cables: Verify that the battery breakers are in the open (Off) position before connecting or disconnecting battery cables. 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 38 NOTE: The settings for String 1 are the factory-default settings. Table 2.4 DIP Switch Settings for 2U Battery Cabinet Strings DIP Switch Position String Cabinet Group 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 39 Figure 2.15 DIP Switch on Rear Panel of 2U Battery Cabinet Item Description Group Number Table 2.5 DIP Switch Settings for Lithium Battery Cabinet Strings DIP Switch Position String No. Cabinet No. Address No. Example 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 40 Vertiv™ Liebert® ITA2 Installer/User Guide Table 2.5 DIP Switch Settings for Lithium Battery Cabinet Strings (continued) DIP Switch Position String No. Cabinet No. Address No. Example 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 41: Communication Connections

    Provides dry contact alarm information, including signals for: On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On Liebert IS-Relay UPS for communication to a remote monitoring system or network-connected Vertiv or third-party shutdown software. The card also Card accepts input signals to shut down the UPS during any operating mode.
  • Page 42: Repo Connection

    If a REPO connection is not required for the UPS, the factory-installed jumper between Pin 9 and Pin 10 must remain installed for the UPS to operate. NOTE: The terminal block wire range is 18AWG ~ 22AWG (0.82 mm ~ 0.33 mm ), and we recommend using 18AWG copper, shielded signal cable.  2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 43: Dry Contact Connections

    The UPS includes five dry contact ports described in Table 2.8 on the next page . The location of the ports is shown in Figure 1.2 on page 4 . For Ports 1 to 4, the I/O dry contact port capacity is 125VAC, 0.5A; 30VDC, 1A 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 44: Connecting Usb Communication Cables

    To connect the serial port communication cable, connect one end of the DB-9 serial port communication cable to the DB-9 serial port on the rear panel of the UPS. Connect the other end to the computer’s DB-9 port. The port uses the RS-232 protocol. 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 45: Connecting Multi-Function Port (Rj-45)

    The multi-function port is a standard RJ-45 connection that supports Modbus/Jbus protocol, and on units with a terminal block battery connector, it connects Vertiv™ temperature and temperature/humidity sensors. When connecting 2U battery cabinets, you must use this port to automatically detect the number of battery strings and for temperature-compensated charging.
  • Page 46 Vertiv™ Liebert® ITA2 Installer/User Guide This page intentionally left blank 2 Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 47: Operation And Display Panel

    Move to previous page, increase value, move left. Down Move to next page, decrease value, move right. Escape Go back. Power Power-on the UPS, power-off the UPS, transfer to Bypass Mode. 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 48: Led Indicators

    An audible alarm accompanies various events during UPS operation. Table 3.3 on the facing page , describes the sounds and their meaning. To silence an alarm, see Silencing the Audible Alarm on page 55 . 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 49: Lcd Menu And Screens

    The menu-driven LCD user interface lets you browse the UPS status, view operating parameters, customize settings, control operation and view alarm/event history. Use the function keys to navigate through the menu, and view statuses or select settings in the screens. Figure 3.3 LCD Menu Structure 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 50: Startup And Ups Mimic Screens

    3.3.1 Startup and UPS Mimic Screens At startup, the UPS executes a system test and displays the Vertiv™ logo screen for 10 to 15 seconds, shown in Figure 3.1 on page 43 . After the test completes, an overview screen shows status information, the active (green) power path and the non- working power path (gray).
  • Page 51 Editing Display and Operation Settings on page 49 , for details on entering the password and editing the setting parameters. Figure 3.7 Monitor and System Tabs on the Settings Submenu 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 52 2. Use the arrow buttons to move the cursor left/right and select a tab, then press Enter to display the log for the selected tab. Figure 3.9 Current and History Log Tabs 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 53: Editing Display And Operation Settings

    Press the up arrow button to change the digit, then press the down arrow button to move to the next digit. 2. Repeat to select each digit, and press Enter to submit the password. Figure 3.11 Password Prompt 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 54 Run Mode Normal, ECO Mode Normal Parallel Redundant No, Yes System Parallel Number 1 – 2 Output Phases 3 Phase 3 Phase Sync Parallel Parameters By HMI Interface Button 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 55 Turn of when UPS on battery for 0-4320 minutes Turn off when backup time less than 0-4320 minutes Turn off when battery capacity less 20-80% than Turn on when power returns for 0-4320 minutes 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 56: Changing The Password

    2. At the password prompt, use the up-arrow to select the first digit, press the down-arrow to move to the next digit, repeat for each digit, then press Enter to access the settings. 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 57 3. Use the arrow buttons to select the Monitor tab, then press Enter. 4. Use the down arrow to highlight Date or Time, then press Enter. 5. Use the up/down arrows to select the date/time, then press Enter to confirm. 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 58 Vertiv™ Liebert® ITA2 Installer/User Guide This page intentionally left blank 3 Operation and Display Panel Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 59: Operating The Ups

    8. After the system checks complete and/or operating parameters are set, press the power button at the front panel display, then use the up/down arrow buttons to confirm Turn on local INV, see Figure 4.1 below . Figure 4.1 Turn on Local INV 4 Operating the UPS Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 60: Transferring From Normal (Inverter) To Bypass Mode

    Use the up/down arrows to select No or Yes, or press ESC to cancel. b. Press Enter to confirm the action. Figure 4.2 Turn Off INV-Bypass Power in Normal Range Figure 4.3 Output Shutdown-Bypass Power Outside Normal Range 4 Operating the UPS Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 61: Transferring From Bypass To Normal (Inverter) Mode

    Use the up/down arrows to select No or Yes, or press ESC to cancel. b. Press Enter to confirm the action. Figure 4.4 Turn on Local INV Figure 4.5 Transfer with Interrupt 4 Operating the UPS Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 62: Transferring To Maintenance Bypass Mode

    Vertiv™ Liebert® ITA2 Installer/User Guide 4.5 Transferring to Maintenance Bypass Mode The transfer procedure puts the UPS in Maintenance Bypass Mode for safe servicing by a Vertiv™ service technician. To transfer from normal operation to maintenance-bypass mode: Press and hold the power button for 2 seconds.
  • Page 63: Remote Emergency Power Off (Repo)

    REPO Connection on page 38 , for connection details. Consult national and local wiring codes to determine if additional REPO is required for the external UPS rectifier and bypass feeds. 4 Operating the UPS Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 64 Vertiv™ Liebert® ITA2 Installer/User Guide This page intentionally left blank 4 Operating the UPS Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 65: Maintenance

    5.2 Routine Maintenance There are no user-serviceable parts in the UPS. Attempting to service the unit yourself can void the warranty. Any routine maintenance other than cleaning, must be performed by a Vertiv™ service technician. Visit http://www.Vertiv.com/en-us/support/, or contact your Vertiv representative.
  • Page 66 Vertiv™ Liebert® ITA2 Installer/User Guide Battery Safety If the battery kit is damaged in any way or shows signs of leakage, contact Vertiv technical support immediately. Handle, transport and recycle batteries in accordance with local regulations. WARNING! Risk of electrical shock. Can cause personal injury and death. When connected together, battery terminal voltage is potentially lethal.
  • Page 67 Vertiv has a service network and recycle system to assist in complying with laws governing waste battery disposal.  Visit http://www.Vertiv.com/en-us/support/ for information about recycling the waste battery.
  • Page 68 (40ms, 60ms, 80ms, 100ms and 200ms are available) Noise, db <55 Panel Display Mode Color LCD IEC/EN62040-1; UL/CSA Safety cULus (UL 1778 5th Edition, CSA No.22.2 107.3) Conduction Emission IEC/EN62040-2; FCC Part 15, Class A Harmonic Current IEC/EN61000-3-12 5 Maintenance Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 69: Specifications

    (3U each cabinet) Battery cabinet with built-in 16-12V (9Ah) batteries BCI0020K03 Battery Cabinet ITA2- (2U each cabinet) Battery cabinet with built-in 16-12V (9Ah) batteries BCI0020K02 ITA2-BCI0020KL1 (1U each cabinet) Lithium Ion Battery Cabinet (6Ah) 6 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 70: Standard Battery Backup Time With A Single Ups

    Table 6.3 Backup Time for 5kVA/5kW VRLA Models in Minutes Load Level Number of Battery 100% Setting 5 kW 4.5 kW 4 kW 3.5 kW 3 kW 2.5 kW 2 kW 1.5 kW 1 kW 0.5 kW 1036 1303 6 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 71 Load Level Number of Battery 100% Settings 5 kW 4.5 kW 4 kW 3.5 kW 3 kW 2.5 kW 2 kW 1.5 kW 1 kW 0.5 kW 1074 1280 1500 1700 6 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 72 Table 6.9 Backup Time for 5kVA/5kW 2U Lithium Models in Minutes Load Level Number of Battery 100% Settings 5 kW 4.5 kW 4 kW 3.5 kW 3 kW 2.5 kW 2 kW 1.5 kW 1 kW 0.5 kW 1348 1788 6 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 73 Load Level Number of Battery 100% Setting 10 kW 9 kW 8 kW 7 kW 6 kW 5 kW 4 kW 3 kW 2 kW 1 kW 1114 1334 1554 1774 6 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 74 Vertiv™ Liebert® ITA2 Installer/User Guide This page intentionally left blank 6 Specifications Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 75: Appendices

    Appears when the output phase is changed. The system requires the user to power Off and check the phase, 3 phase, then power UPS On cable connections, then power On the UPS again to guarantee the safety. Appendices Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 76 Vertiv Technical Support Battery High Cell Volt The maximum battery cell voltage is greater than 3.8V Contact Vertiv Technical Support Battery Internal Communication Battery Internal communication abnormal Contact Vertiv Technical Support Abnormal Appendices Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 77 This alarm will be generated if in the settings menu, if the output frequency None required or change setting to Bypass disabled is set to Auto, BypDisa or 50 Hz, BypDisa or 60 Hz, BypDisa. Auto, BypEna Appendices Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 78 The connected equipment has exceeded the inverter ratings.  The load will disconnect any unauthorized Inverter overload transfer to bypass power if available; otherwise it will shut down. equipment or check if load is properly balanced. Appendices Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 79 UPS has shut down due to activation of the REPO circuit. manually restart the UPS. Restore factory defaults The UPS was manually initiated to reset all settings to the factory defaults None required. Appendices Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 80 UPS has no Output UPS has no output an output, contact Vertiv Technical Support. The UPS firmware version between the control board and display are not Version incompatible Contact Vertiv Technical Support. compatible. Appendices Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 81 Vertiv™ Liebert® ITA2 Installer/User Guide...
  • Page 82 Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2024 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp.