Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
2 Product Description The Vertiv™ Liebert® ITA2 15 to 20 kVA, 50/60 Hz, 208/220 V and 40 kVA, 50/60 Hz, 220/230/240 V UPS (referred as UPS, in this document), the Vertiv™ Liebert® ITA2 Maintenance Bypass Cabinet (referred as MBC, in this document) can provide safe and reliable maintenance bypass function for users.
3.1 Pre-installation Preparation 3.1.1 Installation Tools IMPORTANT! All tools used to install and maintain the Vertiv™ Liebert® ITA2 MBC and equipment must be insulated. The following tools are required to properly install your maintenance bypass cabinet: •...
2. Connect the spacers and the support bases as shown in Figure 3.1 below. Each tower assembly requires two (2) support base/spacer assemblies, one in the front and one in the rear. 3. Place the UPS, battery cabinets, and the Vertiv™ Liebert® ITA2 MBC on the two (2) support base assemblies. Figure 3.1 Support bases...
Page 23
Vertiv™ Liebert® ITA2 MBC Installer/User Guide Figure 3.6 Rack-mounted Vertiv™ Liebert® ITA2 UPS System with Battery Cabinets and Vertiv™ Liebert® ITA2 MBC Item Description Liebert® ITA2 20/40 kVA MBC Liebert® ITA2 20/40 kVA UPS Liebert® ITA2 EBC NOTE: When MBC and EBCs are configurated together with UPS, install the MBC above the UPSs and install EBCs under UPSs, refer to the Figure 3.6...
Ground to the PE screw (next to mA of user input terminal) 3. To connect the Vertiv™ Liebert® ITA2 MBC to a dedicated output distribution panel, refer to the MBC Main Output terminal block in Figure 3.7 on the next page, and connect output cables: •...
Page 26
5. Torque all customer side connections per recommendations in Table 3.1 on page 20, and Table 3.2 on the previous page. 6. Replace the conduit box and secure it. Figure 3.7 Vertiv™ Liebert® ITA2 MBC Single and Dual Input Wiring Diagram of Single MBC Item Description...
Page 27
Vertiv™ Liebert® ITA2 MBC Installer/User Guide Figure 3.8 Vertiv™ Liebert® ITA2 MBC Single and Dual-input Wiring Diagram of 2+0 parallel MBC Item Description User dual input User1 input UPS2 input UPS1 to 2 PE UPS2 dry contact UPS1 dry contact...
Page 28
Vertiv™ Liebert® ITA2 MBC Installer/User Guide Figure 3.9 Vertiv™ Liebert® ITA2 MBC Single and Dual-input Wiring Diagram of 2+1 parallel MBC Item Description User dual input User1 input UPS2 input UPS3 input UPS3 dry contact UPS2 dry contact UPS1 dry contact...
Vertiv™ Liebert® ITA2 MBC Installer/User Guide 3.6 Connecting Communication Cable The Vertiv™ Liebert® ITA2 MBC includes a signal cable to connect to the UPS. NOTE: This chapter describes interconnection between single MBC, 2+0 MBC, or 2+1 MBC and UPS. The 2+0 MBC and 2+1 MBC wiring only need to repeat the steps in this chapter according to the quantity of UPS in system.