C variant pumps have three analog inputs/outputs with different functions. They can be configured through the
web interface (page "pump") or through Modbus.
Input/Output
Run [Default - Mode 1]
SET1
MAX II/Min [Default - Mode
SET2
FB [Default - Mode 1]
SET3
10-STEP SWITCH
Only available in variant Ego 2 (T) easy C. There is a mode selection rotary switch in the terminal box. It can be
rotated by gently inserting a screwdriver into the arrow mark on top and rotating the switch to desired value.
Switch setting is used when the pump turns on! More details about different modes can be found in
communications manual.
Mode
switch
Function
position
0
Free configuration
1
Mode 1
2
Mode 2
3..5
Reserved
Show relay
6
configuration
Change relay
7
configuration
8
Twin reset to factory
9
Reset to factory
Function
Function description
Turning the pump on/off. By default activating with
connection to SET3.
Set the pump to MAX II. settings when SET1 is active and to
1]
min. settings when SET1 is inactive.
10 V voltage output used for activating SET 1 and SET2 by
connecting them to SET3.
Terminal functions are configured over Ethernet interface.
SET1 = RUN input
SET2 = MAX input
SET3 = FB (10.5 V) output, used to supply RUN and MAX inputs. External
voltage source can also be used.
RS-485 = Modbus interface.
SET1 = RUN input
SET2 = SPEED input
SET3 = FB (10.5 V) output, used to supply RUN and MAX inputs. External
5-24 V voltage source can also be used.
RS-485 = Modbus interface
Reserved for future or customer specific use.
LED1 and LED2 will show relay configuration.
Relay configuration will be increased (0->1, 1->2, 2->0) when electricity
is turned on.
LED1 and LED2 will show current relay configuration.
Same as Mode 9, with exception of:
module IP address is set to 192.168.0.246
Twin IP address is set to 192.168.0.245
This mode will set communication interface to default values. Main
purpose is to restore default settings.
NOTE:
Disconnect any SET1, SET2 and SET3 connections when using
this mode to prevent possible harm to controller. SET1, SET2,
SET3 will output test voltages of 10 V, 7 V and 5 V respectively.
RS-485 port is actively driven. Relay will cycle. This is used for
testing purposes.
It is recommended that all module wires are disconnected to
prevent possible harm to external controllers.
Description
35
35