Grounding The Device - Siemens SIMATIC NET RUGGEDCOM RST2228 Equipment Manual

Rugged ethernet switches
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RST2228:
Table of Contents

Advertisement

Installing the device
2.5.3 Grounding the device
Figure 2.19
2.5.3

Grounding the device

In accordance with UL 62368-1/CSA-C22.2 No. 62368-1, the device must be
grounded via the grounding screw between the power module slots.
Figure 2.20
Functional ground
EMC disturbances are diverted to ground via the functional ground. This ensures the
immunity of the data transmission.
The functional ground must be implemented with low impedance. The connection of
the functional ground must be established directly on the mounting plate or the DIN
rail terminal.
34
High AC/DC power supply and low DC power supply
Grounding screw
RUGGEDCOM RST2228
Equipment Manual, 10/2023, C79000-G8976-1359-19