Installing the Device
2.5 Grounding the Device
more information, refer to the "RUGGEDCOM ROS Configuration Manual" for the
RUGGEDCOM RS401.
The following shows the proper relay connections.
1
2
3
Figure 2.7
2.5
Grounding the Device
The RUGGEDCOM RS401 chassis ground terminal uses a #6-32 screw. It is
recommended to terminate the ground connection with a #6 ring lug and torque it
to 1.7 N·m (15 lbf·in).
1
2
3
Figure 2.8
14
1
2
3
Normally Open
Common
Normally Closed
Failsafe Alarm Relay Wiring
1
Stainless Steel Stud
#6-32 Screw
#6 Ring Lug
Chassis Ground Connection
2
3
RUGGEDCOM RS401
Installation Manual, 11/2022, C79000-G8976-1017-12