Page 2
Preface Introduction Installing the Device SIMATIC NET Device Management Rugged Ethernet Switches RUGGEDCOM RS930L Communication Ports Technical Specifications Installation Manual Certification 02/2020 C79000-G8976-1034-06...
Page 3
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommend- ed or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
However, deviations between the product and the documentation may exist. Siemens shall not be liable for any errors or omissions contained herein or for conse- quential damages in connection with the furnishing, performance, or use of this ma- terial.
Siemens Sales representative. Customer Support Customer support is available 24 hours, 7 days a week for all Siemens customers. For technical support or general information, contact Siemens Customer Support through any of the following methods: Online Visit http://www.siemens.com/automation/support-request...
Introduction The RUGGEDCOM RS930L is an 6-port utility-grade, fully managed Ethernet switch with Ethernet over VDSL (EoVDSL) capabilitiies, designed to operate reliably in elec- trically harsh and climatically demanding environments. EoVDSL supports LAN segments of up to 5 km (3.1 mi) over telephone grade cable (or other legacy serial cabling) at up to 35 Mbps (upstream and downstream).
Introduction 1.2 Description • Automatically selects fastest data rate based on distance and quality of cable • Software selectable to be master or slave • Frequency Division Multiplexing (FDM) Rated for Reliability in Harsh Environments • Immunity to EMI and heavy electrical surges •...
Page 12
Introduction 1.2 Description POWER LED ALARM LED EoVDSL Ports Copper (10/100Base-TX) Ethernet Ports RS232 Console Port (Serial) Failsafe Alarm Relay Chassis Ground Connection Power Supply Terminal Block Figure 1.1 RUGGEDCOM RS930L POWER LED Illuminates green when power is supplied to the device. ALARM LED Illuminates red when an alarm condition exists.
Siemens also does not recommend using copper Ethernet ports to interface with de- vices in the field across distances that could produce high levels of ground potential rise (i.e.
This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void. Changes or modifications not expressly approved by Siemens AG could invalidate specifications, test results, and agency approvals, and void the user's authority to operate the equipment.
2.2 Installing the Device in Hazardous Locations Verify all items are included. NOTICE If any item is missing or damaged, contact Siemens for assistance. Installing the Device in Hazardous Locations The RUGGEDCOM RS930L is designed to comply with the safety standards for Class I, Division 2 hazardous locations where concentrations of flammable gases, vapors or liquids may be present, as opposed to normal operating environments.
Installing the Device 2.3 Mounting the Device Mounting the Device The RUGGEDCOM RS930L is designed for maximum mounting and display flexibility. It can be equipped with adapters that allow it to be attached to a DIN rail or panel. IMPORTANT Heat generated by the device is channeled outwards from the enclosure. As such, it is recommended that 2.5 cm (1 in) of space be maintained on all open sides of the device to allow for some convectional airflow.
Page 17
Installing the Device 2.3.1 Mounting the Device on a DIN Rail Mounting the Device To mount the device to a DIN rail, do the following: Hook the top teeth of the adapter onto the DIN rail. Note The adapter features a sliding release with a slot at the bottom for a flathead screwdriver.
Installing the Device 2.3.2 Mounting the Device to a Panel Removing the Device To remove the device from a DIN rail, do the following: Insert a flathead screwdriver into the slot of the sliding release and move it down. DIN Rail DIN Rail Adapter Figure 2.2 Removing the Device from a DIN Rail...
Installing the Device 2.4 Connecting the Failsafe Alarm Relay Place the device against the panel and align the adapters with the mounting holes. Screw Panel Mount Adapter Figure 2.3 Panel Mounting Secure the adapters to the panel with #6-32 screws. Connecting the Failsafe Alarm Relay The failsafe relay can be configured to latch based on alarm conditions.
Installing the Device 2.5 Connecting Power Connect a failsafe device to the terminal block. Normally Closed Common Normally Open Figure 2.4 Failsafe Alarm Relay Wiring Connecting Power The RUGGEDCOM RS930L supports power input from a single high AC/DC or low DC power supply. IMPORTANT •...
Installing the Device 2.5.1 Connecting High AC/DC Power 2.5.1 Connecting High AC/DC Power To connect a high AC/DC power supply to the device, do the following: NOTICE Electrical hazard – risk of damage to equipment Do not connect AC power cables to terminals for DC power. Damage to the power supply may occur.
Page 22
Installing the Device 2.5.1 Connecting High AC/DC Power Connect the positive wire from the power source to the positive/live (+/L) termi- nal on the terminal block. Positive/Live (+/L) Terminal Negative/Neutral (-/N) Terminal Surge Ground Terminal Braided Ground Cable Figure 2.5 Terminal Block Wiring RUGGEDCOM RS930L Installation Manual, 02/2020, C79000-G8976-1034-06...
Installing the Device 2.5.2 Connecting Low DC Power ± ± ± ± Positive Terminal Negative Terminal Surge Ground Terminal Braided Ground Cable Figure 2.6 Terminal Block Wiring – Dual DC Power Supply Inputs Connect the negative wire from the power source to the negative/neutral (-/N) terminal on the terminal block.
Page 24
Installing the Device 2.5.2 Connecting Low DC Power Connect the positive wire from the power source to the positive terminal on the terminal block. ± ± Positive Terminal Negative Terminal Surge Ground Terminal Braided Ground Cable Figure 2.7 Terminal Block Wiring – Single DC Power Supply Inputs Connect the negative wire from the power source to the negative terminal on the terminal block.
Page 25
Installing the Device 2.5.2 Connecting Low DC Power [Optional] If a redundant connection is required, repeat Step 2 Step 3 connect the secondary power inputs. ± ± ± ± Positive Terminal Negative Terminal Surge Ground Terminal Braided Ground Cable Figure 2.8 Terminal Block Wiring – Dual DC Power Supply Inputs Using a braided wire or other appropriate grounding wire, connect the surge ground terminal to the chassis ground connection.
Device Management This section describes how to connect to and manage the device. Connecting to the Device The following describes the various methods for accessing the RUGGEDCOM RS930L console and Web interfaces on the device. For more detailed instructions, refer to the RUGGEDCOM RS930L User Guide for the RUGGEDCOM RS930L.
Device Management 3.2 Configuring the Device The serial console port implements RS232 DCE (Data Communication Equipment) on a DB9 connector. The following is the pin-out for the port: Name Description Reserved (Do Not Connect) Transmit Data Receive Data Reserved (Do Not Connect) Signal Ground Reserved (Do Not Connect) Reserved (Do Not Connect)
Communication Ports The RUGGEDCOM RS930L can be equipped with various types of communication ports to enhance its abilities and performance. Ports 1 to 6 Port 7 Port 9 Figure 4.1 Port Assignment Port Type 1 to 6 Copper Ethernet Ports (10/100Base-TX) 7 and 9 EoVDSL Ports Copper Ethernet Ports...
Page 29
Communication Ports 4.1 Copper Ethernet Ports WARNING Electric shock hazard – risk of serious personal injury and/or equipment inter- ference When shielded cables are used, make sure the shielded cables do not form a ground loop via the shield wire and the RJ45 receptacles at either end. Ground loops can cause excessive noise and interference, but more importantly, create a potential shock hazard that can result in serious injury.
Master and pushed to the Slave. Data flowing from the Master to the Slave is designated downstream, while data flowing from the Slave to the Master is designated upstream. Siemens supports two types of EoVDSL: • Universal EoVDSL Universal EoVDSL ports are Master/Slave selectable and offer symmetric data rates (upstream and downstream) up to 35 Mbps.
Communication Ports 4.2.1 EoVDSL Wiring Pin-Out The following is the pin-out for the RJ11 connectors: Note All RJ11 connectors conform to the standard telephony pin configuration. Description Reserved (Do Not Connect) Reserved (Do Not Connect) Ring Figure 4.4 EoVDSL RJ11 Modem Port Reserved (Do Not Connect) Reserved (Do...
Communication Ports 4.2.2 Configuration and Setup 4.2.2 Configuration and Setup If the RUGGEDCOM RS930L and another device both have Universal EoVDSL ports, configure one device to be the Master and the other the Slave. If both devices have a Long-Reach EoVDSL port, no Master/Slave configuration is necessary, since the ports will already be fixed as Master or Slave.
Page 33
Communication Ports 4.2.3 EoVDSL Performance Note Assuming the distance can support the speed setting, the time to establish a link is typically 15 to 30 seconds. Universal EoVDSL Performance Characteristics On No. 24 AWG Polyethylene Insulated Cable (PIC) twisted-pair wiring, the following performance is typical with Universal EoVDSL: Distance Downstream/Upstream (Mbps)
Technical Specifications This section provides important technical specifications related to the device. Power Supply Specifications Note When determining cable lengths, make sure the minimum input voltage for the pow- er supply is provided at the power source. Hazardous Environments Power Sup- Input Range Internal Isolation...
Technical Specifications 5.2 Failsafe Alarm Relay Specifications Failsafe Alarm Relay Specifications Hazardous Environments Maximum Switching Voltage Rated Switching Current Isolation 30 VDC 1500 V for 1 minute 80 VDC 0.3 A 30 VAC Non-Hazardous Environment Maximum Switching Voltage Rated Switch- Isolation ing Current 30 VDC 2 A, 60 W...
Technical Specifications 5.5 Operating Environment Isolation 2.5 kV Auto-negotiating. Shielded or unshielded. Auto-crossover and auto-polarity. Typical distance. Dependent on the number of connectors and splices. RMS 1 minute. Operating Environment The RUGGEDCOM RS930L is rated to operate under the following environmental con- ditions.
Certification The RUGGEDCOM RS930L device has been thoroughly tested to guarantee its confor- mance with recognized standards and has received approval from recognized regula- tory agencies. Approvals This section details the standards to which the RUGGEDCOM RS930L complies. 6.1.1 This device meets the requirements of the following Canadian Standards Association (CSA) standards under certificate 1550963: •...
Title 21 Code of Federal Regulations (CFR) – Chapter I – Sub-chapter J – Radiolog- ical Health 6.1.4 ISED This device is declared by Siemens AG to meet the requirements of the following ISED (Innovation Science and Economic Development Canada) standard: • CAN ICES-3 (A)/NMB-3 (A) 6.1.5...
6.1.7 RoHS This device is declared by Siemens AG to meet the requirements of the following Ro- HS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
Certification 6.2 EMC and Environmental Type Tests EMC and Environmental Type Tests The RUGGEDCOM RS930L has passed the following Electromagnetic Compatibility (EMC) and environmental tests. EMC Type Tests Test Description Test Levels Severi- ty Levels Enclosure ± 8 kV 61000-4-2 Contact Enclosure Air ±...
Page 44
Certification 6.2 EMC and Environmental Type Tests Test Description Test Levels Severi- ty Levels 1 kV Differential Mode @ 1 MHz Mains Frequency Voltage Signal Ports 30 V Continuous 61000-4-16 300 V for 1 s DC Pow- 30 V Continuous er Ports 300 V for 1 s Ripple on DC Power Supply DC Pow-...
Page 45
Certification 6.2 EMC and Environmental Type Tests Description Test Levels AC Power Ports 5 kV Dielectric Strength Signal Ports 2 kV (Failsafe Relay) DC Power Ports 2 kV AC Power Ports 2 kV Environmental Type Tests Test Description Test Levels Severity Levels IEC 60068-2-1 Cold Temperature Test Ad...
Page 46
Further Information Siemens RUGGEDCOM https://www.siemens.com/ruggedcom Industry Online Support (service and support) https://support.industry.siemens.com Industry Mall https://mall.industry.siemens.com Siemens AG Digital Industry Process Automation Postfach 48 48 90026 NÜRNBERG GERMANY...