MTS9300A Telecom Power (Claro, Colombia,
MTS9304A-AM10A1)
Installation Guide
----End
8.10.4 (Optional) Setting Parameters Before Using SNMP
Management
Prerequisites
Before setting SNMP parameters, obtain the information listed in
the SNMP-based NMS.
Table 8-13 Information obtained from the NMS
Information
SNMP Version
SNMP Port Number
Read Community
Name
Write Community
Name
User Name
MD5/SHA Password
DES/AES Password
Trap Target Address
Trap Port
Trap Community
Procedure
Step 1 Log in to the WebUI.
Issue 01 (2021-05-30)
NO TE
You can set SNMP parameters remotely or locally on the WebUI.
Description
SNMP version and port number used for communication between the
SMU and NMS. The SNMP version can be SNMPv1, SNMPv2c, or
SNMPv3.
If you use SNMPv1 or SNMPv2c, enter the read and write community
names that comply with the NMS. Otherwise, the SMU will not connect
to the NMS.
The read community name must be different from the write community
name.
To enhance the security, you need a user name and password for
authentication if you use SNMPv3. After the authentication succeeds, the
SMU can communicate with the NMS.
IP address and port number used for reporting alarm trap packets.
If you use SNMPv1 or SNMPv2c, this parameter is the community name
used for reporting alarm trap packets.
NO TE
● The standard protocols SNMPv1 and SNMPv2 have security risks. You are advised to use
the secure protocol SNMPv3.
● The standard encryption algorithms MD5 and DES have security risks. You are advised
to use the secure encryption algorithms SHA and AES.
Copyright © Huawei Technologies Co., Ltd.
8 Commissioning
Table 8-13
from
67