Huawei MTS9300A Installation Manual page 72

Hide thumbs Also See for MTS9300A:
Table of Contents

Advertisement

MTS9300A Telecom Power (Claro, Colombia,
MTS9304A-AM10A1)
Installation Guide
Main
Second-Level
Menu
Menu
Step 3 Set the IP Addresses and Ports for the active servers of the NetEco on the SMU's
LCD.
Table 8-11 NetEco parameters
Main Menu
Second-
Level Menu
Parameters
Comm.
Settings
Parameters
----End
Networking Mode 2: RS485 Port
Step 1 Set Port Mode to Manual, Protocol Type to M/S Protocol, Baud Rate to 9600,
and Comm. Address to 3.
Table 8-12 Communications parameters
Main Menu
Second-
Level
Menu
Parameters
Comm.
Settings
Parameters
Issue 01 (2021-05-30)
Third-Level
Menu
Default
Gateway
Third-Level
Fourth-Level
Menu
Menu
Network
NetEco Primary
Parameters
IP
NetEco Port
Number
Third-
Fourth-Level
Level
Menu
Menu
Serial
Northbound
Port
M/S
Baud Rate
Protocol
Comm.
Address
Copyright © Huawei Technologies Co., Ltd.
Default Value
Settings
192.168.0.1
Set this parameter
according to the gateway
address provided by the
network administrator.
Default
Value
192.168.0.10
31220
Fifth-Level
Menu
Port Mode
Protocol Type
NOTE
This parameter
is displayed
only when Port
Mode is set to
Manual.
-
-
8 Commissioning
Settings
Set an IP
address for the
active NetEco
server.
Set a port for
the NetEco.
Default
Settings
Value
Automatic
Manual
M/S
M/S
Protocol
Protocol
9600
9600
3
3
66