MTS9300A Telecom Power (Claro, Colombia,
MTS9304A-AM10A1)
Installation Guide
Step 2 Access the System Settings page and set SNMP.
●
●
●
Step 3 Click Add in SNMP Trap.
●
●
Step 4 In Mib files, click Export to export the Mib file and then import it into the NMS.
----End
8.11 Connecting the AC Power Supply
Procedure
Step 1 Switch on the AC input circuit breaker and measure the output voltage of the AC
input circuit breaker. The value should range from 85 V AC to 300 V AC.
Step 2 Check that the RUN indicator on the rectifier is steady on.
Step 3 Set all circuit breakers to the appropriate status based on site requirements.
Step 4 Observe the power system for 15 minutes. If no alarm (except the door status
alarm) is generated on the SMU during this period, the current and voltage for
batteries and loads are normal.
----End
Issue 01 (2021-05-30)
NO TE
The preset user name is admin, and the preset password is Changeme.
There are two NMSs and the SNMP versions are SNMPv1 or SNMPv2c and
SNMPv3: Set SNMP Version in SNMP to ALL, set SNMP Port, Read
Community Name, and Write Community Name, then click Add in
SNMPv3, set User Name, MD5/SHA Password, and DES/AES Password, and
click Confirm.
SNMPv1 or SNMPv2c: Set SNMP Version in SNMP to SNMPv1&SNMPv2c,
set SNMP Port, Read Community Name, and Write Community Name, and
click Confirm.
SNMPv3: Set SNMP Version in SNMP to SNMPv3, click Add in SNMPv3, set
User Name, MD5/SHA Password, and DES/AES Password, and click
Confirm.
If SNMP Version is set to SNMPv1 or SNMPv2c, set Trap Target Address,
Trap Port, and Trap Community.
If SNMP Version is set to SNMPv3, set Trap Target Address, Trap Port, and
SNMPv3 User Name.
NO TE
The SNMP version here can be different from the version in
NO TE
If there is only one NMS, perform
Copyright © Huawei Technologies Co., Ltd.
Step 4
once only.
8 Commissioning
Step
2.
68