Power Connection - Altronix NetWay5P Series Installation Manual

5-port hardened poe+ switches
Table of Contents

Advertisement

NetWay5PWPN/NetWay5PWP/NetWay5PWPX:
1. Remove backplane from enclosure prior to drilling. Do not discard hardware.
Note: Make sure that hardware will not interfere with components of the circuit board.
2. Mark and drill desired inlets on the enclosure to facilitate wiring. Maximum NEMA type 4X rated fittings
to be used are 0.5". Follow manufacturer's specifications for the appropriate size opening.
Note: Inlets for conduit fittings should only be made on the bottom of the enclosure.
To facilitate wire entry utilize weather-tight NEMA rated connectors (supplied), bushings, and cable.
3. Clean out the inside of enclosure before remounting circuit boards/backplane.
4. Mounting NEMA4/4X rated enclosure (Enclosure Dimensions, pg. 8-11):
Wall mount: Mount unit in desired location. Mark and drill holes to line up with the top and bottom hole of
the enclosure flange. Secure enclosure with appropriate fasteners (e. g. screws and anchors;
bolts and locking nuts, etc.) that are compatible with mounting surface and are of sufficient
length/construction to ensure a secure mount (Fig. 4, pg. 7).
Pole Mount: Refer to Fig. 5 - 10, pg. 7.
5. Mount backplane in enclosure with hardware.
NetWay5PX:
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two (2) upper fasteners and screws in the wall with the screw heads protruding.
Place the enclosure's upper keyholes over the two (2) upper screws; level and secure. Mark the position of
the lower two (2) holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the
enclosure's upper keyholes over the two (2) upper screws. Install the two (2) lower screws and make sure to
tighten all screws (Enclosure Dimensions, pg. 11). Secure enclosure to earth ground.

Power Connection:

NetWay5PWP, NetWay5PWPX, NetWay5PX:
1. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Fig. 2a, pg. 4). Green "AC" LED on
power supply board will turn on. Use 14 AWG or larger for all power connections.
Secure green wire lead to earth ground.
Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input,
Battery Wires). Minimum 0.25" spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or
servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to
qualified service personnel.
2. When the use of stand-by batteries is desired, they must be lead acid or gel type. If batteries are housed in a
weather-proof enclosure (NetWay5PWP, NetWay5PWPX), it must be properly ventilated. Use Altronix Vent2 kit.
Connect battery to terminals marked [– BAT +] (Fig. 2g, pg. 4). Use two (2) 12VDC batteries connected
in series for 24VDC operation (battery leads included) Use batteries - Casil CL1270 (12V/7AH), CL12120
(12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of an
appropriate rating. When batteries are not used, a loss of AC will result in the loss of the output voltage.
3. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 2b, pg. 4) supervisory relay outputs.
4. To delay AC reporting for 2 hrs. set DIP switch [AC Delay] to OFF position (Fig. 2c, pg. 4).
To delay AC reporting for 1 min. set DIP switch [AC Delay] to ON position (Fig. 2c, pg. 4).
Note: Must be set to ON position for Burglar Alarm Applications.
5. To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position (Fig. 2c, pg. 4).
To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position (Fig. 2c, pg. 4).
6. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals
will cause [DC] output to shutdown (Fig. 2d, pg. 4).
7. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching
[Trigger EOL Shutdown] (Fig. 2e, pg. 4).
NetWay5P, NetWay5PWPN:
1. Mount NetWay5P/NetWay5PWPN in the desired enclosure/location (mounting hardware is included).
2. NetWay5P/NetWay5PWPN can be powered by a UL Listed 12/24VDC power source, e.g. Altronix eFlow
power supply/charger or a solar panel with nominal 24V (~18-35V) output.
Input/Data Connections:
1. Connect a Data source to the [Data Input] RJ45 jack (Fig. 1b, pg. 4).
2. Connect Access Control boards, Altronix LINQ units or other IP devices to the [Port 1 - Port 4] RJ45 jacks
(Fig. 1c, pg. 4). Refer to the corresponding Installation Guides for details.
NetWay5P Series Installation Guide
- 3 -

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NetWay5P Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Netway5pwpNetway5pxNetway5pwpxNetway5pwpnNetway5p

Table of Contents