UPS5000-E-180 kVA
User Manual (Integrated UPS, 30 kVA Power
Modules)
Figure 4-22 Removing cable hole protection panels
Step 2 Open the rear door, and remove the insulation panels at the rear of the cabinet.
Figure 4-23 Removing insulation panels
Step 3 Connect a ground cable to the UPS cabinet.
● Before connecting cables, ensure that all UPS input switches are turned off.
● You need to prepare terminals onsite. The length of the copper wire stripped
should be the same as that of the part of the terminal that covers the
conductor.
Issue 05 (2024-01-30)
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
80