Huawei UPS5000-E-180 kVA User Manual page 99

Hide thumbs Also See for UPS5000-E-180 kVA:
Table of Contents

Advertisement

UPS5000-E-180 kVA
User Manual (Integrated UPS, 30 kVA Power
Modules)
No.
14
15
16
17
18
19
Issue 05 (2024-01-30)
Item
Whether the SPD switch is
turned on
Cabinet circuit breaker
status
Fuse installation
Whether the cable route
hinders the operation of
components or damages
the insulation layer of
cables
Foreign matter cleaning
inside the cabinet
Dust covers on the cabinet
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
Expected Result
If the SPD switch is OFF, turn it on.
The circuit breakers in the cabinet are
OFF.
Fuses have been installed in the cabinet.
The cable route does not hinder the
operation of components or damage the
insulation layer of cables.
The inside and outside of the cabinet are
free from conductive dust or other
sundries.
1. There is no foreign matter (such as
copper wires and screws) on the top
of the cabinet.
2. There is no foreign matter on the
copper bar terminals.
3. There is no foreign matter around
switch terminals.
4. There is no foreign matter on the
bottom plates of the cabinet.
5. There is no foreign matter on the rear
module subrack.
The dust covers on the cabinet are
intact. Any damaged air filter should be
replaced promptly.
Do not remove the dust covers during
construction or before power-on.
Otherwise, the equipment may be
damaged.