Installing the Device
2.5.2 Connecting Low DC Power
2.
3.
4.
5.
20
Note
For secure, reliable connections under severe shock or vibration, use M3.5 ring
tongues with a maximum outer diameter of 7 mm (0.28 in). Make sure no bare
metal is exposed beyond the safety cover.
Connect the positive wire from the power source to the positive (+) terminal on
the terminal block.
Connect the negative wire from the power source to the negative (-) terminal on
the terminal block.
For screw terminal blocks, install the safety cover.
Screw
1
Safety Cover
2
Screw Terminal Block
3
RUGGEDCOM RX1536 Device
4
Figure 2.13
Assembling the Safety Cover
Using a #10 ring tongue and #10-32 screw, secure the ground terminal on the
power source to the ground connection on the device. Make sure the screw is
tightened to 2.4 N·m (21 lbf·in).
4
3
2
1
RUGGEDCOM RX1536
Equipment Manual, 10/2023, C79000-G8976-1488-07