Siemens SIMATIC ET 200PA SMART+ DI 32x24VDC PA Equipment Manual
Siemens SIMATIC ET 200PA SMART+ DI 32x24VDC PA Equipment Manual

Siemens SIMATIC ET 200PA SMART+ DI 32x24VDC PA Equipment Manual

Hide thumbs Also See for SIMATIC ET 200PA SMART+ DI 32x24VDC PA:

Advertisement

SIMATIC ®
ET 200PA SMART+
DI 32x24VDC PA
Equipment Manual
6DL1161-6BL00-0PH1
06/2023
A5E51654125-AA
Security information
Preface
2D Matrix code (QR code /
EAN code)
Product overview
Connection
Parameters
Displays and interrupts
Technical specifications
Drivers, parameters,
diagnostics messages and
address space
1
2
3
4
5
6
7
8
A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SIMATIC ET 200PA SMART+ DI 32x24VDC PA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Siemens SIMATIC ET 200PA SMART+ DI 32x24VDC PA

  • Page 1 Security information Preface 2D Matrix code (QR code / EAN code) SIMATIC ® Product overview ET 200PA SMART+ DI 32x24VDC PA Connection Parameters Equipment Manual Displays and interrupts Technical specifications Drivers, parameters, diagnostics messages and address space 6DL1161-6BL00-0PH1 06/2023 A5E51654125-AA...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Security information..........................5 Preface ..............................7 2D Matrix code (QR code / EAN code) ....................9 Product overview ..........................11 I/O module......................... 11 Accessories ........................12 Terminal blocks........................13 Terminal blocks with potential distributors (L+ potential) ............ 13 Connection............................
  • Page 4 Table of contents Interrupts .......................... 27 Technical specifications ........................29 Drivers, parameters, diagnostics messages and address space ............33 Parameter assignment ....................... 33 Parameter assignment and structure of the module/channel parameters......34 Diagnostic messages......................36 Maintenance events......................37 Hardware interrupts ......................38 Address space ........................
  • Page 5: Security Information

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
  • Page 6 Security information DI 32x24VDC PA Equipment Manual, 06/2023, A5E51654125-AA...
  • Page 7: Preface

    Preface [ID: 151041112203] Validity of the documentation This manual describes the following I/O module: System family I/O module Article number SIMATIC Distributed I/O System ET 200PA SMART+ DI 32x24VDC PA 6DL1161-6BL00-0PH1 It supplements the system manual for the ET 200PA SMART+ Distributed I/O System. Functions that generally relate to the system are described in this manual.
  • Page 8 Preface DI 32x24VDC PA Equipment Manual, 06/2023, A5E51654125-AA...
  • Page 9: Matrix Code (Qr Code / Ean Code)

    The 2D matrix code on the product is a coded representation of the product-specific article number. Access to product-related information For reading the 2D matrix code, SIEMENS offers an app for mobile use. Information about the app and the download can be found on the Internet: "Mobile use via app (https://support.industry.siemens.com/cs/ww/en/sc/2067)".
  • Page 10 2D Matrix code (QR code / EAN code) DI 32x24VDC PA Equipment Manual, 06/2023, A5E51654125-AA...
  • Page 11: Product Overview

    Product overview I/O module [ID: 151041124619] Definition The DI 32x24VDC PA I/O module is a digital input module with 32 power inputs for process control. In addition to the technical specifications, this module has the following properties: • Sink input (PNP, active power) •...
  • Page 12: Accessories

    Product overview 4.2 Accessories Description The I/O module consists of the following components: ① ⑧ Function status and firmware ver‐ LED for diagnostics sion ② ⑨ Serial number Module type and designation ③ Article number     ④ LED for supply voltage  ...
  • Page 13: Terminal Blocks

    The terminal blocks provide the process terminals (push-in terminals) for the connection of components, such as devices. Description For details on the terminal blocks that can be used, please refer to the current manual SIMATIC, Distributed I/O System ET 200PA SMART+ at https://support.industry.siemens.com/ (https:// support.industry.siemens.com/) Note The terminal blocks are not included in the scope of delivery of the I/O module and must be ordered separately.
  • Page 14 Product overview 4.4 Terminal blocks with potential distributors (L+ potential) Description Use the following terminal block to connect 2-wire sensors: Article No. Function/parameter 6DL1193-6TP00-0DP0 Allow new potential group (light terminal block) 6DL1193-6TP00-0BP0 Use potential group of the left module (dark terminal block) DI 32x24VDC PA Equipment Manual, 06/2023, A5E51654125-AA...
  • Page 15: Connection

    Connection Pin assignment (1-wire connection) [ID: 151041183755] Definition The pin assignment provides information about the arrangement and identification of the terminals when wiring a connector. Description The general pin assignment is structured as follows: Terminal Assignment Terminal Assignment Explanations DI a /DI.0+ DI a /DI.1+ DI a /DI.n+: Input signal, channel n (0…7) DI b /DI.n+: Input signal, channel n+8 (8…15)
  • Page 16: Pin Assignment (2-Wire Connection)

    Connection 5.3 Pin assignment of the terminal block with D-SUB connector Pin assignment (2-wire connection) [ID: 151041211403] Definition The pin assignment provides information about the arrangement and identification of the terminals when wiring a connector. Description The pin assignment on the left side of the terminal blocks with potential distributor corresponds to the following assignment: Pin assignment (1-wire connection) (Page 15) The potential distributor with the following terminals is located on the right side of the...
  • Page 17 Connection 5.3 Pin assignment of the terminal block with D-SUB connector Description The general pin assignment of a terminal block field with push-in terminals paired with the 37- pin D-SUB connector is as follows: Terminal block with push-in terminals Terminal block with D-SUB connector Signals Scheme Signals...
  • Page 18: Sample Connection Scheme For 1-Wire Connection

    Connection 5.4 Sample connection scheme for 1-wire connection Note Wiring of the connections • When wiring the connections on the D-SUB connector, note the shift starting with no. 17. • The power supply is connected to the terminal block with D-SUB connector via the separate X21 connector.
  • Page 19: Example Connection Scheme For Di-2 Wire Sensor Connection

    Connection 5.7 Schematic circuit diagram Example connection scheme for DI-2 wire sensor connection [ID: 151041253899] Example DI.n+ This connection variant is only permitted with terminal blocks of the type "potential distributor". Example connection diagram for sensor connection with external power supply [ID: 151041285771] Example DI.n+ This connection variant is only permitted with terminal blocks of the type "potential...
  • Page 20 Connection 5.7 Schematic circuit diagram Description The block diagram for the I/O module is structured as follows: Terminal Input electronics Channel diagnostics LEDs Reverse polarity protection 1P2, 2P2 1P1, 2P1 Feed module supply with bright terminal block DI 32x24VDC PA Equipment Manual, 06/2023, A5E51654125-AA...
  • Page 21: Parameters

    Parameters Parameter types [ID: 151041347979] Definition You define and thereby influence the functions supported by the module operation of the I/O module via the parameter types. Module/channel parameters [ID: 151041357579] Definition Module/channel parameters are specific parameters whose configuration can affect the entire module or channel.
  • Page 22: Explanation Of The Module/Channel Parameters

    Parameters 6.3 Explanation of the module/channel parameters Parameters Value range Default Parameter re‐ Efficiency range assignment in Potential group (Page 23) Use potential Module • Potential group of the left mod‐ group of the left ule (dark gray terminal block) module • New potential group (light gray terminal block) •...
  • Page 23: Channel Activated

    Parameters 6.3 Explanation of the module/channel parameters 6.3.4 Channel activated [ID: 151041407371] Definition Specifies whether a channel is activated or deactivated. 6.3.5 Hardware interrupts positive edge [ID: 151041416971] Definition Specifies if a hardware interrupt should be generated for a rising edge. 6.3.6 Hardware interrupts negative edge [ID: 151041426571] Definition Specifies if a hardware interrupt should be generated for a negative edge.
  • Page 24: Double-Width Terminal Block

    Parameters 6.3 Explanation of the module/channel parameters 6.3.8 Double-width terminal block [ID: 151041445771] Definition Select the "Double-width terminal block" parameter in the hardware properties for the I/O module. DI 32x24VDC PA Equipment Manual, 06/2023, A5E51654125-AA...
  • Page 25: Displays And Interrupts

    Displays and interrupts Status and error displays of the I/O module DI 32x24VDC PA [ID: 151041458315] Definition The LED displays are status and fault indicators. Diagnostic messages and maintenance events, as well as their possible causes and solutions, are described in the diagnostic messages and maintenance events. Diagnostic messages (Page 36).
  • Page 26: Leds

    Displays and interrupts 7.2 LEDs LEDs 7.2.1 DIAG LED [ID: 151041498123] Definition The DIAG LED provides you diagnostic information. Description The diagnostic display of the DIAG LED is as follows: DIAG LED Meaning The supply voltage of the ET 200PA SMART+ is disrupted or switched off. Module is not configured.
  • Page 27: Channel Status Led

    Displays and interrupts 7.3 Interrupts 7.2.3 Channel status LED [ID: 151041648139] Definition Regardless of the parameter assignment, the channel status LED status shows the signal level at the input terminal. It lights up starting at approximately 10 V of terminal voltage. Description The channel status LED indicates the following statuses: LED channel Meaning status...
  • Page 28 Displays and interrupts 7.3 Interrupts Description The I/O module generates a diagnostics interrupt at the following events: • Supply voltage L+ missing • Parameter assignment error • Hardware interrupt lost • Channel/component temporarily unavailable • Wire break • Retentive memory in carrier module defective •...
  • Page 29: Technical Specifications

    Technical specifications [ID: 151041725195] Technical specifications of the DI 32×24VDC PA Article number 6DL1161-6BL00-0PH1 General information   Product type designation DI 32x24VDC PA Firmware version   • FW update possible Usable terminal block see the system manual Product function   Yes; I&M 0 •...
  • Page 30 Technical specifications Article number 6DL1161-6BL00-0PH1 Short-circuit protection Yes; When using TB type P0 Power loss   Power loss, typ. 1.6 W; Max. 2.8 W (all inputs "1") Address area   Address space per module   4 byte; + 4 bytes for QI information •...
  • Page 31 Technical specifications Article number 6DL1161-6BL00-0PH1 Alarms   Yes; channel by channel • Diagnostic alarm Yes; channel by channel • Hardware interrupt Diagnoses   • Diagnostic information readable Yes; Module-wise • Monitoring the supply voltage – parameterizable Yes; Channel-by-channel, optional protective cir‐ •...
  • Page 32 Technical specifications Make sure that the supply and input voltages of the ET 200PA SMART+ IO Device are generated safely separately: Nominal value: 24 VDC +-20% ( Cycle time The cycle time describes the time slice in which signals from the inputs are acquired and processed.
  • Page 33: Drivers, Parameters, Diagnostics Messages And Address Space

    Drivers, parameters, diagnostics messages and address space Parameter assignment [ID: 151041757323] Parameter assignment in the user program You can reconfigure individual channels of the module in RUN without this having an effect on the other channels. Changing parameters in RUN The parameters are transferred to the module with the "WRREC" instruction via data record 128. Output parameter STATUS of the WRREC If errors occur when transferring parameters with the "WRREC"...
  • Page 34: Parameter Assignment And Structure Of The Module/Channel Parameters

    Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment and structure of the module/channel parameters Parameter assignment and structure of the module/channel parameters [ID: 151041766283] Structure of data record 128 Data record 128 has a length of 76 bytes. It contains module parameters as well as channel or technology parameters of the 32 channels;...
  • Page 35 Drivers, parameters, diagnostics messages and address space A.2 Parameter assignment and structure of the module/channel parameters Header information and module parameters The following figure shows the configuration of the header information and module parameters. Byte 0 Minor version Major version Reserved Byte 1 Number of following parameter structures Byte 2...
  • Page 36: Diagnostic Messages

    Drivers, parameters, diagnostics messages and address space A.3 Diagnostic messages x = 12 + (channel number * 2); with channel number = 0…31 All unused bits and the bits or bytes marked as "reserved" must be set to zero. You activate a channel parameter by setting the corresponding bit to "1" or the corresponding value.
  • Page 37: Maintenance Events

    Drivers, parameters, diagnostics messages and address space A.4 Maintenance events Diagnostics mes‐ Error code Assign‐ Meaning Remedy sage ment Parameter assign‐ Module • Parameter assignment does not • Correct the parameter assign‐ ment error match the terminal block used ment • Incorrect parameter assignment •...
  • Page 38: Hardware Interrupts

    Drivers, parameters, diagnostics messages and address space A.6 Address space Hardware interrupts [ID: 151041975947] Hardware interrupts The DI 32×24VDC PA generates a hardware interrupt for the following events: • At a rising edge (signal change from 0 to 1) • At a falling edge (signal change from 1 to 0) Interrupt OBs are called automatically if an interrupt occurs.
  • Page 39 Drivers, parameters, diagnostics messages and address space A.6 Address space Address space The following figure shows the mapping of the address space of the DI 32x24VDC PA. Table A-1 Address space of the DI 32x24VDC PA IB x + DI15 DI14 DI13 DI12 DI11 DI10 DI23...
  • Page 40 Drivers, parameters, diagnostics messages and address space A.6 Address space DI 32x24VDC PA Equipment Manual, 06/2023, A5E51654125-AA...
  • Page 41: Index

    Index Value status Evaluating, 39 DI 32x24VDC PA Equipment Manual, 06/2023, A5E51654125-AA...
  • Page 42 Index DI 32x24VDC PA Equipment Manual, 06/2023, A5E51654125-AA...

This manual is also suitable for:

6dl1161-6bl00-0ph1

Table of Contents