Led Indication; Default Settings - Pepperl+Fuchs 7500 User Manual

Purge system
Hide thumbs Also See for 7500:
Table of Contents

Advertisement

7500 S
M
 P
erieS
anual
Note
To save settings and exit setup mode, hold the set button to return to normal mode.
Changes to settings take effect immediately. Entering the incorrect password will exit
setup mode.
WArNINg!
Do not change program setting in hazardous areas.
4.1.2

LED Indication

K1
K2
P/SV

4.2. Default Settings

Display
PASSWORD / SET
PURGE / PROGRAM
PURGE / TIME
For model 7500-01-*
ENCLOSUR / PRESS P1
ENCLOSUR / PRESS P2
ENCLOSUR / PRESS P3
ENCLOSUR / PRESS P4
For model 7500-03-*
ENCLOSUR / PRESS P1
ENCLOSUR / PRESS P2
ENCLOSUR / PRESS P3
ENCLOSUR / PRESS P4
LEAKAGE / HYST
44
rograMMing
LED Color
Green
Amber
Blue/amber
Description
Enter password to access purge
settings
Up to 5 programs to select
Time required for purging
Enclosure pressure P1
Enclosure pressure P2
Enclosure pressure P3
Enclosure pressure P4
Enclosure pressure P1
Enclosure pressure P2
Enclosure pressure P3
Enclosure pressure P4
Compensates for leakages
Description
Contact K1 is energized
Contact K2 is energized
Blue: safe pressure
Amber: valve on
Default Values
0000
3
00:30
P1 for gas 0.12 inch w.c. (0.30 mbar)
P1 for dust 0.52 inch w.c. (1.29 mbar)
0.8 inch w.c. (1.99 mbar)
2.5 inch w.c. (6.22 mbar)
4.5 inch w.c. (11.2 mbar)
P1 for gas 0.23 inch w.c. (0.57 mbar)
P1 for dust 0.63 inch w.c. (1.57 mbar)
0.8 inch w.c. (1.99 mbar)
2.5 inch w.c. (6.22 mbar)
4.5 inch w.c. (11.2 mbar)
0.2 inch w.c. (0.5 mbar)