Pepperl+Fuchs 7500 User Manual page 12

Purge system
Hide thumbs Also See for 7500:
Table of Contents

Advertisement

7500 S
M
 P
erieS
anual
Output
Output I
Connection
Output type
Contact loading
Output II
Connection
Output type
Contact loading
Output III
Connection
Output type
Inrush current
Contact loading
Indicators/settings
LED indicator
Pneumatic parameters
Protective gas supply
Pressure requirement
Enclosure pressure
Directive conformity
Electromagnetic conformity
Directive 2014/30/EU
RoHS
Directive 2011/65/EU
(RoHS)
Conformity
Ambient conditions
Ambient temperature
Storage temperature
Altitude
12
d
roducT
eScriPTion
K1 terminals, 1 x NO
enclosure power contacts
5 A at 250 V AC, 5 A at 30 V DC, relays must be externally fused
Inrush current: 50 A
K2 terminals, 1 x NO
alarm and control contacts
5 A at 250 V AC, 5 A at 30 V DC, relays must be externally fused
Inrush current: 50 A
SV, terminals, L1 powered contact
Solenoid manifold, contact
5 A
0.5 A at 250 V AC, 0.5 A at 30 V DC, relays must be externally fused
K1: Green—Contact K1 is energized (enclosure contacts)
K2: Amber—Contact K2 is energized (alarm/control contacts)
P/SV: Blue—Safe pressure P1 (minimum enclosure pressure)
P/SV: Amber—Solenoid manifold is energized (purging pressure
compensation)
compressed air or inert gas, 40 μm filter, free from oil
supply pressure: 20...120 psig (1.4...8.2 bar)
0...10 in wc (0...25 mbar)
EN 61326-1, FCC CFR 47, part 15, subpart B:2017, Class A
ICES-003, Issue 6:2016, Class A ITE
EN IEC 63000:2018
-40 ... 70 °C (-40 ... 158 °F) at T4 / T80 °C
-40 ... 65 °C (-40 ... 149 °F) at T5 / T75 °C
-40 ... 50 °C (-40 ... 122 °F) at T6 / T60 °C
-40 ... 80 °C (-40 ... 176 °F)
max. 2000 m