Technician Settings P122 to P187
P122 – Cool Proportional output threshold time (seconds) (FC only)
Range: 0...100 seconds
Default: 60 seconds
P123 – Heat Proportional output threshold time (seconds) (FC Only!)
Range: 0...100 seconds
Default: 60 seconds
P160 – Minimum compressor ON time (AC only)
Range: 0...20 minutes
Default: 2 minutes
P161 – Minimum compressor OFF time (AC only)
Range: 0...20 minutes
Default: 13 minutes
P170 – Economizer low limit temperature
Range: 9...27ºC / 48...80ºF
Default: 17ºC / 63ºF
P198 – Not in use
P200 – Restore defaults
- Press the [+] button – the display will change from "00" to "01".
- Press the [On/Off] button to restore default settings.
- The thermostat will turn Off.