Technician Settings

Enter Technician Settings mode:
1. Adjust the setpoint temperature to 10ºC or 50ºF.
2. Press and hold the [C/F] button for 10 seconds to enter Technician Settings mode. "P01" will appear on display.
View objects and make adjustments:
Use the [Mode] button to step forward between different settings.

Use the [Fan] button to step backward between different settings.

Press the [On/Off] button to exit Technician Settings and return to normal display.

If no button is pressed for 60 seconds, the thermostat will automatically exit Technician Settings and return to normal display.

Use the [+] and [-] buttons to make adjustments when required.

P01 – Offset for temperature readings calibration
Range:
-6...+6°C / -9...+9°F.
Default: 0°C / 0°F.
Note: The offset will influence both internal
or external sensors.
P02 – Setpoint limit for cooling
Range:
5...35°C / 41...95°F.
Default: 10°C / 50°F.
Note: The thermostat will stop cooling regardless of
the user's setpoint
P03 – Setpoint limit for heating
Range:
5...35°C / 41...95°F.
Default: 30°C / 86°F.
Note: The thermostat will stop heating regardless of
the user's setpoint
P04 – Enable/Disable the option to lock the [Fan] button
"LF" + " "
[Fan] button can be locked
"LF" only
[Fan] button cannot be locked
Note: When enabled, press and hold both [-] and [Fan] buttons
for 7 seconds to actually lock the buttons.
- 40 -
Offset for temperature calibration
(°C)
(°F)
Setpoint limit for cooling
(°C)
(°F)
Setpoint limit for heating
(°C)
(°F)
[Fan]
[Fan]
Can
Cannot
be locked
be locked