Technician Settings
Enter Technician Settings mode:
1
Adjust the setpoint temperature to 10ºC or 50ºF.
2
Press and hold the [C/F] button for 10 seconds to enter Technician Settings mode. "P01" will appear on the
display.
View objects and make adjustments:
•
Use the [Mode] button to step forward between different settings.
•
Use the [Fan] button to step backward between different settings.
•
Press the [On/Off] button to exit Technician Settings and return to normal display.
•
If no button is pressed for 60 seconds, the thermostat will automatically exit Technician Settings and return to
normal display.
•
Use the [+] or [-] button to make adjustments when required.
Technician Settings P01 to P03
P01 –
Offset for temperature readings calibration
Range: -6...+6°C / -9...+9°F.
Default: 0°C / 0°F.
Note: The offset will influence both internal or external sensors.
P02 –
Setpoint limit for cooling
Range: 5...35°C / 41...95°F.
Default: 10°C / 50°F.
Note: The thermostat will stop cooling regardless of the user's setpoint
P03 –
Setpoint limit for heating
Range: 5...35°C / 41...95°F.
Default: 30°C / 86°F.
Note: The thermostat will stop heating regardless of the user's setpoint