Technician Settings P89 to P99

P89 – De-ice in heat – cut-in temperature (AC only)
Range: -9.5...+8°C / 15...46°F
Default: 0°C / 32°F
The outdoor unit coil temperature in which de-icing will start.
P90 – De-ice in heat – cut-out temperature (AC only)
Range: 2...20°C / 35...68°F
Default: 16°C / 61°F
The outdoor unit coil temperature in which de-icing will stop.
P91 – Compressor delay (AC only)
Range: 0...360 Seconds
Default: 240 Seconds
DIP Switch SW3.5 must be in "OFF" position – compressor delay enabled!
P98 – Display setpoint only (hide room temperature)
"00" -
Display both setpoint and room temperatures
"01" -
Display only the setpoint temperature
P99 – One or Two setpoints (for cool and for heat)
"00" -
One setpoint for cooling and heating
"01" -
Two setpoints, one for cool and one for heat