Carrier TB-24 Installation And Operation Manual

Carrier TB-24 Installation And Operation Manual

Comfortvu bacnet thermostat
Hide thumbs Also See for TB-24:
Table of Contents

Advertisement

Quick Links

ComfortVu™ BACnet
Thermostat Model Standard
TB-24 (24 Vac)
Installation and Operation Guide
©2024 Carrier. All rights reserved. • Catalog No. 11-808-722-01 • 1/26/2024

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TB-24 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Carrier TB-24

  • Page 1 ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac) Installation and Operation Guide ©2024 Carrier. All rights reserved. • Catalog No. 11-808-722-01 • 1/26/2024...
  • Page 2 Verify that you have the most current version of this document from www.hvacpartners.com, the Carrier Partner Community website, or your local Carrier office. Important changes are listed in Document revision history at the end of this document. ©2024 Carrier. All rights reserved.
  • Page 3: Table Of Contents

    Contents Overview ..................................1 Specifications................................2 TBPL-24-H Dimensions ............................... 4 Technician Settings Index ............................5 Operating Instructions ..............................7 Quick Guide ................................7 Turning the thermostat ON and OFF ........................8 Selecting temperature scale ..........................8 Adjusting the Setpoint temperature ........................9 Selecting system mode ............................
  • Page 4 Contents Technician Settings P83 to P88 ........................50 Technician Settings P89 to P99 ........................51 Technician Settings P101 to P109 ......................... 52 Technician Settings P114 to P119 ......................... 53 Technician Settings P122 to P187 ......................... 54 Alarms and indications ............................. 55 Document revision history ............................
  • Page 5: Overview

    BACnet Thermostat’s data. The TB-24 thermostat has a white plastic enclosure with an LCD display and buttons for user control. It has on-board temperature sensing, and its on-board inputs and outputs are used to control equipment and optional external sensing devices.
  • Page 6: Specifications

    • If not using an electrical box, flush-mount thermostat to wall (no wallplate needed). Weight 4.8 oz (0.14 kg) ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 7 Styrene and 1,3 - Propane sultone, which are known to the State of California to cause cancer. For more information, go to www.p65warnings.ca.gov. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 8: Tbpl-24-H Dimensions

    TBPL-24-H Dimensions ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 9: Technician Settings Index

    P72 – Fan VFS High speed percent in heating P37 – Freeze protection cut-out set point P74 – VFS Medium speed differential ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 10 P198 – Not in use P200 – Restore defaults Press the [On/Off] button or wait 60 seconds to return to normal display. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 11: Operating Instructions

    Operating Instructions Quick Guide ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 12: Turning The Thermostat On And Off

    Press the [On/Off] button to turn the thermostat ON or OFF. Selecting temperature scale e [C/F] button to switch between temperature scales. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 13: Adjusting The Setpoint Temperature

    In Auto mode, the active mode icon (Cool or Heat) will flash. • Auto mode is not available in 2-Pipe system configuration. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 14: Selecting Fan Speed (For 2 And 3 Fan Speeds Configuration)

    When ON, the fan will run on demand for cooling or heating. • When OFF, the fan will run continuously. Note: Auto fan cannot be selected in Fan only mode. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 15: Locking The Thermostat Buttons

    Refer to technician parameter P18 “Door switch or key tag configuration” Economy by Key-tag Refer to technician parameter P18 “Door switch or key tag configuration” ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 16: Freeze Protection

    Economizer will start when, and run as long as, both of the following conditions are satisfied: Teconomizer temperature < Room temperature - (Cool differential band / 2) Room Temperature > Setpoint temperature ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 17 When Economizer is active, the “Cool” symbol will appear (or flash when active) on display and the “Fan” symbol will flash. Economizer Active ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 18: Weekly Program

    If a clock icon does not appear, ensure that the set-point temperature is not 10/11ºC or 50/52ºF, press ○ and hold the button to activate the program. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 19 At any time during the programming procedure, press the [On/Off] button to exit and return to normal display. Any changed values will be saved. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 20 3. Press the [C/F–Prog] button again. The MINUTES will flash. 4. Use the [+] and [-] buttons to adjust the start time minutes of the first event. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024...
  • Page 21 3. Press the [C/F–Prog] button again. The MINUTES will flash. 4. Use the [+] and [-] buttons to adjust the start time minutes of the first event. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024...
  • Page 22 Follow the steps above for the other schedule events of the same daily period (P2 for two events per day, or P2, P3 and P4 for four events per day). • Follow the steps above for all daily periods. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 23: Mac Address And Bacnet Device Instance Number

    By default, the BACnet Device Instance Number is generated automatically by the thermostat (Vendor ID + MAC address). For example, Carrier Corporation vendor ID is 16, and if the MAC address is 075, the BACnet Device Instance Number is 16075.
  • Page 24 Subsequent reads/writes of this value will need to be done with the new device instance: bacnet://16113/AV:42/present_value, or bacnet://16113/BACnetDeviceInstanceNumber ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 25: Installation

    Install the cove to the back panel; first the two bottom tabs and then the top tongue. Push until tight against the wall. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 26: Wiring Terminals

    Remote economy switch / External PIR Power supply: 24 Vac CAUTION Do not connect line voltage to a thermostat that does not show the following symbol: ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 27: Dip Switch And Jumper Configurations

    ON = End of line SW1.1 through SW1.6, and SW3.1 through SW3.8 See Wiring and DIP switch/jumper settings (page 26). ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 28: Ac Configurations

    1 2 3 1 2 3 Fan speeds ○ ○ ○ ○ ○ ○ Economizer • Yes ○ Option ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 29: Fc Configurations For 4-Pipe Systems / Floor Heating

    ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ Economizer • • Floor heating • Yes ○ Option ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 30: Wiring And Dip Switch/Jumper Configurations 1 To 4 - Ac Systems

    See drawing for DIP switch and jumper locations (page 23). Control – Fan on/off, Heat elements, Heat pump, Compressors, Economizer: 24 Vac, 0.5A max ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 31: Wiring And Dip Switch/Jumper Configurations 5 To 7 - Ac Systems

    Fan VFS: 0-10 Vdc, 0.5 mA Not isolated Control – Fan on/off, Heat elements, Heat pump, Compressors, Economizer: 24 Vac, 0.5A max ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 32: Wiring And Dip Switch/Jumper Configurations 8 To 9 - Ac Systems

    See drawing for DIP switch and jumper locations (page 23). Control – Fan on/off, Heat elements, Heat pump, Compressors, Economizer: 24 Vac, 0.5A max ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 33: Wiring And Dip Switch/Jumper Configurations 10 To 13 - Fc Systems - 2-Pipe

    Fan VFS, PID valves: 0-10 Vdc, 0.5 mA Not isolated Control – Fan on/off, Heat elements, Cool/Heat valves, Economizer: 24 Vac, 0.5A max ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 34: Wiring And Dip Switch/Jumper Configurations 14 To 17 - Fc Systems - 4-Pipe

    Fan VFS, PID valves: 0-10 Vdc, 0.5 mA Not isolated Control – Fan on/off, Heat elements, Cool/Heat valves, Economizer: 24 Vac, 0.5A max ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 35: Wiring And Dip Switch Configurations 18 To 21 - Fc Systems - 4-Pipe

    Fan VFS, PID valves: 0-10 Vdc, 0.5 mA Not isolated Control – Fan on/off, Heat elements, Cool/Heat valves, Economizer: 24 Vac, 0.5A max ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 36: Wiring And Dip Switch/Jumper Configuration 22 - Fc Systems - 4-Pipe

    See drawing for DIP switch and jumper locations (page 23). PID valves: 0-10 Vdc, 0.5 mA Not isolated Control – Fan on/off, Heat elements, Cool/Heat valves: 24 Vac, 0.5A max ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 37: Technician Settings

    Range: 5…35°C / 41…95°F. Default: 30°C / 86°F. Note: The thermostat will stop heating regardless of the user’s setpoint ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 38: Technician Settings P04 To P07

    In normal display, press and hold the [Mode] button for 7 seconds to unlock/relock these buttons. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 39: Technician Settings P08 To P10

    Note: To view T3 on the BACnet Thermostat, see Technician Settings P84. P10 – Window contact (terminals IN1,0) polarity “01” - Normally open “00” - Normally closed ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 40: Technician Settings P11 To P15

    “01” - Thermostat turns off when unoccupied and remains off when re-occupied. “02” - Thermostat uses economy setpoints when unoccupied. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 41: Technician Settings P16 To P25

    Normally open “01” - Normally closed P25 – Economy setpoint for cooling Range: 5…35°C / 41…95°F Default: 30°C / 86°F ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 42: Technician Settings P26 To P30

    “01” - LCD Backlight OFF P30 – Beeper ON or OFF “01” - Beeper ON “00” - Beeper OFF ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 43: Technician Settings P31 To P34

    Range: 0…120 seconds Default: 0 seconds (no delay) P34 – Fan OFF delay in heating Range: 0…120 seconds Default: 30 seconds ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 44: Technician Settings P35 To P42

    The display will change from “00” to “01” and back to “00”. P42 – Adjust filter alarm delay time counter (hours) Range: 0…999 hours Default: 0 hours (0 = Disable) ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 45: Technician Settings P43 To P44

    The fan will stop if the temperature on T3 sensor drops below the cut-out temperature. See Technician Settings P08/P09. Range: 12...35°C / 54…95°F Default: 32°C / 90°F ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 46: Technician Settings P45 To P46

    Range: 0.5...5°C / 1…10°F Default: 1°C / 2°F P46 – Cool differential band offset Range: -5…+5°C / -9…+9°F Default: 0°C / 0°F ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 47: Technician Settings P47 To P48

    Range: 0.5...5°C / 1…10°F Default: 1°C / 2°F P48 – Heat differential band offset Range: -5…+5°C / -9…+9°F Default: 0°C / 0°F ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 48: Technician Settings P49 To P51

    Range: 0...10°C / 0…20°F Default: 2°C / 4°F P51 – Shift between Heating stages Range: 0...49°C / 0…98°F Default: 2°C / 4°F ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 49: Technician Settings P52 To P57

    Default: 0% Minimum valve opening. P57 – Heat proportional high limit (FC only) Range: 0...100% Default: 100% Maximum valve opening. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 50: Technician Settings P60 To P64

    Range: 0…600 seconds Default: 5 seconds P64 – Time off-delay between cooling stages (AC only) Range: 0…600 seconds Default: 1 seconds ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 51: Technician Settings P65 To P70

    P69 – Fan VFS High speed percent in cooling Range: 60...100% Default: 90% P70 – Fan VFS Low speed percent in heating Range: 0...30% Default: 30% ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 52: Technician Settings P71 To P75

    P74 – VFS Medium speed differential Range: 10...50% Default: 35 P75 – VFS High speed differential Range: 10...50% Default: 35 ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 53: Technician Settings P76 To P79

    P78 – Fan VFS Low limit in heating Range: 0...100% Default: 0% P79 – Fan VFS High limit in heating Range: 0...100% Default: 100% ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 54: Technician Settings P83 To P88

    P88 – De-ice in heat break time (AC only) Range: 10… 30 Minutes Default: 25 Minutes The time interval between de-icing cycles. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 55: Technician Settings P89 To P99

    “00” - One setpoint for cooling and heating “01” - Two setpoints, one for cool and one for heat ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 56: Technician Settings P101 To P109

    US Program: Event start time, Mode, Fan speed, Setpoints (one or two) “01” - Eu program: Event start time, Stop time ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 57: Technician Settings P114 To P119

    P118 – Cool PID Kd (FC only) Range: 0...100% Default: 1% P119 – Heat PID Kd (FC only) Range: 0...100% Default: 1% ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 58: Technician Settings P122 To P187

    - Press the [+] button – the display will change from “00” to “01”. - Press the [On/Off] button to restore default settings. - The thermostat will turn Off. ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide...
  • Page 59: Alarms And Indications

    Window contact - Remote economy switch Economy by: • External PIR • Communication Economy by door switch Economy by key-tag ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 60: Document Revision History

    Added CE and C-Tick icons to Compliance specification Installation Changed step B and illustrations Technician Settings, P122 and P123 Changed from percent to time (seconds) ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential CARRIER CORPORATION ©2024 Installation and Operation Guide All rights reserved...
  • Page 61 Carrier ©2024 · Catalog No. 11-808-722-01 · 1/26/2024...

This manual is also suitable for:

Tbpl-24-h