To Adjust Occupancy Settings - Carrier Connect 33CONNECTSTAT43FX Installation Manual

Wi-fi thermostat
Table of Contents

Advertisement

Using the menu for advanced features

To adjust occupancy settings

Setting
SET OCC FAN—Operates the fan in AUTO or ON during occupied periods
NOTE If the installer configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
REMINDER! The AUTO setting is a violation of ASHRAE 90.1 and Title 24 but is a
feature of the thermostat for building owners that mandate auto fan operation during
occupied periods for energy conservation purposes.
SET UNOC FAN—Operates the fan in AUTO or ON during unoccupied periods
NOTE If the installer has configured the thermostat for non-programmable operation
and remote occupancy is disabled, this setting is not available.
UNOCC COOL—The cool setpoint during unoccupied periods
NOTES
The minimum value you can set is limited by the unoccupied heat setpoint (cool
setpoint cannot be less than the heat setpoint) and the installer setting for MIN
COOL SETPOINT.
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
UNOCC HEAT—The heat setpoint during unoccupied periods
NOTES
The maximum value is limited by the unoccupied cool setpoint (heat setpoint cannot
be greater than the cool setpoint) and the installer setting for MAX HEAT SETPOINT.
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
OCC COOL—The cool setpoint during occupied periods
NOTES
The minimum value is limited by the occupied heat setpoint (cool setpoint cannot
be less than the heat setpoint) and the installer setting for MIN COOL SETPOINT.
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
OCC HEAT—The heat setpoint during occupied periods
NOTES
The maximum value is limited by the occupied cool setpoint (heat setpoint cannot
be greater than the cool setpoint) and the installer setting for MAX HEAT SETPOINT.
If the installer has configured the thermostat for non-programmable operation and
remote occupancy is disabled, this setting is not available.
Carrier Connect™ Wi-Fi Thermostat 33CONNECTSTAT43FX
Installation Guide
22
Default/Range
D:
AUTO
R:
AUTO
ON
D:
AUTO
R:
AUTO
ON
D:
85°F
R:
52 to 90°F
D:
62°F
R:
50 to 88°F
D:
75°F
R:
52 to 90°F
D:
70°F
R:
50 to 88°F