Technician Settings P65 To P70 - Carrier TB-24 Installation And Operation Manual

Comfortvu bacnet thermostat
Hide thumbs Also See for TB-24:
Table of Contents

Advertisement

Technician Settings P65 to P70

P65 – Fan VFS proportional band in cooling
Range: 2...10°C / 4...20°F
Default: 2°C / 4°F
0-10V fan speed from off closed to fully running.
P66 – Fan VFS proportional band in heating
Range: 2...10°C / 4...20°F
Default: 2°C / 4°F
0-10V fan speed from off closed to fully running.
P67 – Fan VFS Low speed percent in cooling
Range: 0...30%
Default: 20%
P68 – Fan VFS Medium speed percent in cooling
Range: 30...60%
Default: 50%
P69 – Fan VFS High speed percent in cooling
Range: 60...100%
Default: 90%
P70 – Fan VFS Low speed percent in heating
Range: 0...30%
Default: 30%
ComfortVu™ BACnet Thermostat Model Standard TB-24 (24 Vac)Carrier Proprietary and Confidential
Installation and Operation Guide
47
CARRIER CORPORATION ©2024
All rights reserved

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tbpl-24-h

Table of Contents