RDZ CHR 400 CoRe Installation & Technical Manual page 19

Air handling units, mechanical ventilation with heat recovery appliance
Table of Contents

Advertisement

OVERVIEW OF THE ELECTRONIC BOARD UNIT
2
Descriptions
1
5 electro-mechanical relay digital outputs (max 2 A)
2
230 VAC power supply
3
6 analogue inputs
4
5 dry contact digital inputs
5
2 analogue outputs
6
Switch SW2
7
Switch SW1
8
R-BUS port
9
MODBUS port
ON
1 2 3 4 5 6 7 8
SW1 SETTING - SETTAGGIO SW1
DIP Description - Descrizione
Air Flow Selector
(CHR without controllers)
1
Selettore Portate Aria
(CHR senza controllori)
2
3
4
Not Used
Non Utilizzati
5
6
7
Type of Communication
8
Tipo di Comunicazione
(*) see paragraph 5.3 - vedi paragrafo 5.3
DO0
DO1
DO2
N
L
AI0 AI1 AI2 AI3 AI4 AI5
3
SW1
Value - Valore
Def.
OFF= Nominal
flow rates - Portate
Nominali
OFF
ON= Reduced Flow
Rates - Portate
Ridotte (*)
OFF
OFF
OFF
Not Used
Non Utilizzati
OFF
OFF
OFF
OFF (-)
OFF
ON (Wi - KNX)
PANORAMICA SCHEDA ELETTRONICA A BORDO
1
DO3
DO4
DI0 DI1 DI2 DI3 DI4
AO0
4
5
Descrizione
5 uscite digitali a relè elettromeccanico (max 2A)
Alimentazione 230 VAC
6 ingressi analogici
5 ingressi digitali a contatto pulito
2 uscite analogiche
Switch SW2
Switch SW1
porta R-BUS
porta MODBUS
SW2 SETTING - SETTAGGIO SW2
DIP
Description - Descrizione
1
2
Modbus address
3
(1 to 63)
Indirizzo Modbus
4
(da 1 a 63)
5
6
Transmission speed
7
Velocità di trasmissione
No. of stop bits
8
N° bit di stop
19
B - RX (-)
9
A - TX (+)
GND
CH
8
CL
GND
7
6
AO1
SW2
ON
1
2 3 4 5 6 7 8
Value - Valore
Default: 9
(DIP 1 e 4 = ON
OFF = 19200 Bit/s
ON = 9600 Bit/s
OFF = 2 bit (Wi)
ON = 1 bit (KNX)
Def.
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF