Setup for auto-test, auto-arm and opening/closing times
LOCATION 51 - AUTOTEST CONTROL (4 segments, numerical data)
Segment 1
Segment 2
Segment 3
Segment 4
LOCATION 52 - OPENING TIME/AUTOMATIC DISARMING TIME (2 segments, numerical data)
Location 52 contains the time (in 24 hour format) when the NX-8 will enable the disarm
capability for codes designated as 'arm only after closing'. This time is only valid on those days
programmed in location 54. This is also the time when the panel will automatic disarm.
Note: Opening time must be earlier than closing time so that auto arm, Aux. outputs, or code
authorisation can function properly.
Segment 1
Segment 2
LOCATION 53 - CLOSING TIME/AUTOMATIC ARMING TIME (2 segments, numerical data)
Location 53 contains the time (in 24 hour format) when the NX-8 will disable the disarm
capability for codes designated as 'arm only after closing'. This is also the time when the
automatic arming sequence will begin (if this option is enabled in location 55).
Note: Opening time must be earlier than closing time so that auto arm, Aux. outputs, or code
authorisation can function properly.
Segment 1
Segment 2
NX-8-EUR Installation manual
Program a "1" if the interval is to be in hours; program a "0" for days. Add
a "2" to suppress the daily test or a "3" to suppress the hourly test if any
report has been sent
Program the autotest interval from 1-255 hours/days
Program the autotest report hour in 24 hour format (if the interval is in
hours, this segment Is ignored)
Program the autotest report time, number of minutes after the hour
Program the hour of the opening time
Program the minutes after the hour of the opening time
Program the hour of the closing / auto arm time
Program the minutes after the hour of the closing / auto arm time