Chimney
Flue
Insulated
Chimney
Masonry
I
f thIs stove Is not Installed properly
,
thIs rIsk
please follow the dIrectIons for InstallatIon carefully
Required Installation Components:
A. Chimney Cap
A.
B. Insulated Chimney
C. Storm Collar
D. Roof Flashing
C.
E. Ceiling Support Box or Joist Shield/Firestop
D.
Spacer
F. Chimney Connector
For venting vertically into a Class A chimney, a single
wall pipe (at least 24 gauge) may be used in the room
E.
where the stove is installed. Refer to the manufac-
turer's instructions for the connection to the listed
chimney. The chimney/stove pipe must not be small-
er than 6" (15cm) in diameter.
For venting directly into a masonry chimney or
through a thimble, the top of the single wall pipe
must be at least 18" (46cm) below a combustible
ceiling and must conform to NFPA 211 guidelines
and methods. Please see the diagram to the left.
Connector Pipe
18" (46cm) below ceiling
Min.
2" (5cm)
Min.
2" (5cm)
For rear venting or other unlisted configu-
rations, consult the local building codes
and follow the NFPA 211 guidelines.
If the stovepipe is fitted with a baffle, it
must be manually operated, visibly placed
for ease of use, and must not close com-
pletely. Consult your chimney expert if you
have any questions.
mportant note:
I
Please ensure that there is easy access to
the chimney cleanout door.
,
a home fIre may result