Accessories Setup; Access Of Configuration Parameters; Airflow And Fire Dampers; Fire And Fireplace Protection Inputs - Salda AMBERAIR COMPACT S-CX H Operation, Installation & Maintenance Instructions

Table of Contents

Advertisement

5.5. ACCESSORIES SETUP

Some accessories or functions of the connected external components must be additionally configured to work properly in the Air Handling unit's
system. Configuration can be implemented via the web interface, SALDA AIR mobile application or ST-SA-Control remote panel. Mobile applica-
tion can be downloaded from the Google Play Store (for Android devices) and Apple App Store (for iOS devices).

5.5.1. ACCESS OF CONFIGURATION PARAMETERS

To access configuration parameters using the web interface follow the steps below (additional device required: MB-Gateway):
• Configure the MB-Gateway device to your local network structure (if needed) and connect it to the AmberAir Compact unit as well as to your
local network. More information is provided in the MB-Gateway launch guide.
• In the web browser of the device on the same local network open http://salda.lt/mcb/control/service.htm.
• Enter MB-Gateway IP, LOGIN (by default – admin), PASS (by default – admin), unit ID (by default - 1), and press SET.
• To access unit configuration parameters enter the service user menu password (by default – 4444) and press the KEY symbol.
To access configuration parameters with ST-SA-Control remote panel follow the steps below:
• Connect SA-Control to the AmberAir Compact unit, turn on the unit and wait for the panel to load up. Access your unit automatically or manually
(adjuster password by default – 1111). More information is provided in the ST-SA-CONTROL manual.
• To access unit configuration parameters in the main window select MENU
To access configuration parameters with SALDA AIR mobile app follow the steps below (additional devices required: MB-Gateway, WIFI router):
• Configure the MB-Gateway device to your local network structure (if needed) and connect it to the AmberAir Compact unit as well as to your
local network with WIFI access. More information is provided in the MB-Gateway launch guide.
• Download and install the SALDA AIR application on a smartphone or tablet.
• Turn on the unit
• Connect to your WIFI access point.
• Start the SALDA AIR application and access your unit automatically or manually (units SLAVE ID by default – 1; MB-Gateway PORT and IP
depends on its configuration; adjuster password by default – 1111).
• To access unit configuration parameters in the main window select MENU
More information about operating a particular control environment can be found in its provided documentation.

5.5.2. AIRFLOW AND FIRE DAMPERS

• In the SERVICE menu select DAMPERS.
• Set supply and extract air damper type and opening time.
• Set the fire damper type and other available parameters.
• In the SERVICE menu select DIGITAL INPUTS.
• Set the input types of fire damper switches.
• In the SERVICE menu select SAVE CHANGES/SAVE SETTINGS and RESTART (AHU).

5.5.3. FIRE AND FIREPLACE PROTECTION INPUTS

FIRE PROTECTION INPUT configuration:
• In the SERVICE menu select MAIN.
• Set the FIRE PROTECTION 1 parameters.
AMBERAIR COMPACT S-CX v2023.3
> SERVICE. Enter the password (by default – 4444) and press OK.