Salda AMBERAIR COMPACT S-CX H Operation, Installation & Maintenance Instructions page 11

Table of Contents

Advertisement

On the installation side, there must be enough place (1.5x product depth) for the door to open for service (replacing filters, removing the fan,
cleaning the heat exchanger, etc.).
• Installation works should be carried out by qualified and trained staff only.
• When connecting air ducts, consider the labels on the casing of the unit.
• Before connecting to the air duct system, the connection openings of the ventilation unit should be closed.
• When connecting the ducts, the air-flow direction indicated on the device housing should be observed.
• Do not connect the bends close to the connection flanges of the unit. The minimum distance of the straight air duct between the unit and the first
branch of the air duct in the supply and exhaust air ducts must be 3xD, where D is the diameter of the air duct.
• It is recommended to use flexible connections (accessories). This will reduce the vibration transmitted by the unit to the air duct system and
environment.
• If the ventilation unit is a wall-mounted device, it may transmit noise vibrations to the premises. Though the level of noise generated by the
fans is admissible, we recommend mounting the unit at a distance of 400 mm from the nearest wall. Where this is not possible, we recommend
mounting the unit on the wall of the room where the level of noise is not significant.
• Ducts are connected to the unit in such a way that they could be easily disassembled, and the coil could be removed from the unit when carrying
out maintenance, service and/or repair works.
The protective film is used to protect the unit during transportation. It is recommended to remove the film, otherwise, oxida-
tion signs may occur.
UNIT PLACING AND MOUNTING POSITIONING REQUIREMENTS
FLOOR MOUNTING ON ADJUSTABLE FOOT (ORDERED AS AN ACCESSORY)
• The installation should be performed having positioned the units in the horizontal direction only.
• Install the antivibration feet.
• They must be adjusted without a gradient.
AMBERAIR COMPACT S-CX v2023.3
Fig. 4.7.1 Horizontal floor-mounting positions on floor (W=400 mm)
L
1,5xL
1,5xL
Fig. 4.7.2 Min. distance to open the door - 1,5xL
Fig. 4.7.3 Floor mounting
L
W
EN |
11

Advertisement

Table of Contents
loading

Table of Contents