Backfeed Protection Device Specifications - Huawei UPS2000-H User Manual

Hide thumbs Also See for UPS2000-H:
Table of Contents

Advertisement

UPS2000-H-(6 kVA-10 kVA)
User Manual

5.4.1 Backfeed Protection Device Specifications

This equipment does not have a built-in backfeed protection device. You can add a
backfeed protection device for the input. The protection solution is as follows: If
you do not install a backfeed protection device for the input, add a warning label
on the main power disconnection device that supplies power to the UPS to warn
electrical maintenance personnel. The warning label contains information similar
to the following: "This circuit supplies power to the UPS. Disconnect the UPS
before cable connection." In addition, check whether dangerous voltages exist on
all main power connection terminals.
When battery mode is unavailable or the mains fails, certain voltage or energy in
the UPS may flow back directly, or through a leakage path, to an input terminal.
To minimize the risk of electric shocks caused by reverse feeding, install a
backfeed protection device for the UPS input.
Table 5-4 Rated voltage and current of contacts of the backfeed protection
contactor
Model
UPS2000-H-6KRTL-L
UPS2000-H-10KRTL-L
Table 5-5 Control relay parameters
Recommended Model
HONGFA: HF18FF/012
OMRON: MY2N-J DC12V
Panasonic: HJ2-L-DC12V
Issue 03 (2023-08-20)
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Installation and Cable Connection
Rated Voltage and
Rated Current
220 V AC/230 V AC/240
V AC, 50 A
220 V AC/230 V AC/240
V AC, 80 A
Requirements
Contact type: normally closed (NC)
Breaking capacity: 250 V AC, 5 A
Coil specifications: 12 V, rated current
< 1 A
Recommended
Backfeed Protection
Device Model
(Schneider Contactor)
Contactor LC1-D50A
Contactor LC1-D80A
87