Step 3 The parallel configuration parameters are adaptive. Choose Config > System
Parameters > Parallel system to manually set the parameters as required.
Issue 03 (2023-08-20)
Item
Description
System time
Synchronizes the system
time to the UPS.
Battery type
Specifies the type of
batteries connected to the
UPS.
Single
Specifies the voltage of
battery
each battery in a battery
voltage (V)
string connected in series.
Set this parameter based
on the actual configuration.
This parameter is
configurable in non-
battery mode.
Batteries in a
Specifies the number of
battery
batteries in a battery string.
string
Set this parameter based
on the actual configuration.
This parameter is
configurable in non-
battery mode.
Single
Specifies the capacity of
battery
each battery in a battery
capacity
string connected in series.
(Ah)
This parameter is
configurable in non-
battery mode.
Number of
Specifies the number of
battery
battery strings connected in
strings
parallel. This parameter is
configurable in non-
battery mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On Commissioning
Setting
Value Range
-
-
VRLA batt.
VRLA batt.,
Lithium batt.
The default
value is VRLA
batt.
Set as
2, 6, and 12.
required.
The default
value is 0.
Set as
The value
required.
range
depends on
the voltage of
a single
battery. The
default value
is 0.
Set as
7–1000. The
required.
default value
is 0.
Set as
1–4. The
required.
default value
is 0.
111