UPS2000-H-(6 kVA-10 kVA)
User Manual
7.2.1 Monthly Maintenance
Table 7-4 Monthly maintenance checklist
Item
Battery
managem
ent alarm
Battery
appearanc
e
Battery
operating
temperatu
re
Issue 03 (2023-08-20)
Expected Result
No battery
management alarm
is generated.
1. The surface is
clean and free of
stains.
2. The battery
terminals are
intact.
3. Batteries are free
from damage
and cracks.
4. Batteries are free
from acid
leakage.
5. Batteries are not
deformed or
bulged.
1. The standard
battery operating
temperature is
25°C.
2. Battery charge
and discharge
conditions meet
the requirements
specified in the
battery
specifications.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Troubleshooting
Identify the alarm cause
based on the alarm
information.
If an exception occurs,
contact technical support.
1. Identify the cause of
the abnormal battery
operating temperature.
2. If the fault persists,
contact technical
support.
7 Maintenance
Maintenance
Interval
Monthly
Monthly
Monthly
122