Huawei UPS2000-H User Manual page 52

Hide thumbs Also See for UPS2000-H:
Table of Contents

Advertisement

UPS2000-H-(6 kVA-10 kVA)
User Manual
Table 3-3 Mains input electrical specifications
Item
Power system
Rated input
voltage
Input voltage
range
Rated frequency
Frequency range
Input power
factor
Generator input
capacity
Overvoltage
category
Table 3-4 Bypass input electrical specifications
Item
Power system
Input voltage
Issue 03 (2023-08-20)
6 kVA
Single-Phase
Input
1Ph (L/N) + PE
220 V AC/230 V
AC/240 V AC
Phase voltage: 80
V AC to 280 V AC
(When the
ambient
temperature
ranges from –5°C
to +40°C, the load
is linearly derated
from 100% to
40% when the
voltage ranges
from 176 V AC to
80 V AC.)
50 Hz/60 Hz
40–70 Hz
≥ 0.99 (100% resistive load)
Minimum: 1.35 times of the UPS rated capacity
OVC II
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 kVA
Single-Phase
Input
1Ph (L/N) + PE
220 V AC/230 V
AC/240 V AC
Phase voltage: 80
V AC to 280 V AC
(When the
ambient
temperature
ranges from –5°C
to +40°C, the load
is linearly derated
from 100% to
40% when the
voltage ranges
from 176 V AC to
80 V AC.)
Specifications
Single-phase, three-wire
220 V AC/230 V AC/240 V AC
3 Technical Specifications
Three-Phase
Input
3Ph (L1/L2/L3/N)
+ PE
380 V AC/400 V
AC/415 V AC
Line voltage: 138
V AC to 484 V AC
(When the
ambient
temperature
ranges from –5°C
to +40°C, the load
is linearly derated
from 100% to
40% when the
voltage ranges
from 176 V AC to
80 V AC.)
44

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups2000-h-6krtl-lUps2000-h-10krtl-l

Table of Contents