2 Self-Supervision Messages
2.3 Self-Supervision – Information Messages
2.3
Self-Supervision – Information Messages
Description
SI 1...3
SI 4 Inval Password
SI 5 Inval Conn. Pwd
SI 6 Settings changed
SI 7 Firmware Update
SI 8 Device restart
SI 9 Remote Access
SI 10 Password changed
SI 11 ADC values wrong
10
Information
– reserved for future use –
Information that a wrong (access level) password
was entered.
Information that a wrong connection password
was entered.
Information that the settings (e.g. the protection
parameters) have been modified.
Information that a new device firmware has been
installed.
Information that the device has been restarted.
Information that a PowerPort-E connection via
network (e.g. Ethernet) has been established.
Information that a password has been changed
by the user.
ADC values wrong
www.eaton.com
Corrective Action
The message value is the number of wrong passwords
that have been entered within some time.
The message value is the number of wrong connection
passwords that have been entered within some time.
The message value is the number of setting changes that
have been made within some time. (A setting change is
counted whenever new parameter values are transferred
to the device or saved at the HMI panel.)
The message value shows the reason for the device
restart.
Device Start-up Codes: 1=Restart initiated by power
supply; 2=Restart initiated by the User; 3=Set on
defaults (Super Reset); 4=Restart by the debugger;
5=Restart because of configuration change; 6=General
failure; 7=Restart initiated by System Abort (host
side); 8=Restart initiated by watchdog timeout (host
side); 9=Restart initiated by System Abort (dsp side);
10=Restart initiated by watchdog timeout (dsp side);
11=Power supply failure (short term interruption) or
power supply voltage too low; 12=illegal memory access.
The message value is the number of password changes
that have been made within some time.
The displayed timestamp is probably relevant with
respect to messages
SE 38
or
SE
39. Since this message
always occurs together with these error messages you
should get in contact with our service-team.