Intelligent Addressable Control Panel
FX6000 Installation and Operation Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FX6000 and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton FX6000

  • Page 1 Intelligent Addressable Control Panel FX6000 Installation and Operation Manual...
  • Page 2: Table Of Contents

    Additional instructions for electromagnetic compatibility . . . . . . . . . . . . . . . .32 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 3 CABle & WIrInG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 4 Up/downloading using PC software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 5 Global flashing LED On/Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 6 Wall sounder wiring (FXN538LPS, FXN539LPS) . . . . . . . . . . . . . . . . . . . . . . 112 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 8 THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES . In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental...
  • Page 9 That is why we offer you so many ways to get the support you need . Whether it is by phone, fax, or email, you can access Eaton’s support information 24 hours a day, seven days a week . Our wide range of services is listed below . You should contact your local distributor for product pricing, availability, ordering, expediting and repairs .
  • Page 10 IF BAtterY Is rePlACed BY An InCorreCt tYPe dIsPose oF tHe used BAtterIes ACCordInG to tHe InstruCtIons (Appendix page 129) . this product must only be disposed of in accordance with the Weee directive . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 11: Introduction

    Introduction Introduction FX6000 provides all of the sophisticated features required of a leading edge analogue addressable fire system along with the simple operation and neat installation demanded by installers and building users . The panel can be flush or surface mounted and the generously sized metal back box allows ample facilities for rear or top cable entries .
  • Page 12: System Design Guidelines

    5. Final commissioning A minimum of two weeks notice is required from receipt of Address Schedule and Commissioning request form for a Eaton Service Engineer to attend site and implement/oversee the final commissioning procedures (see Commissioning section), in conjunction with the installer .
  • Page 13: Loop Loading System Verification

    Addressable Detectors: Point Addressable Multi-Mode Heat FXN725 400003FIRE-0006X Sensor Addressable Optical Smoke Sensor 100 FXN723 400002FIRE-0005X Addressable Photo-Thermal Sensor 100 FXN722 400004FIRE-0007X Addressable Detectors: Speciality Addressable Reflective Beam MAB100R MAB100R Detector 50-100m FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 14 Addressable Wall Sounder Beacon 95 FXN539LPS FXN539LPS Addressable Wall Sounder Beacon FXN539LPSWP FXN539LPSWP (Weatherproof) Addressable Wall Sounder VAD CASB393 CASB393 (White Flash) Addressable Wall Sounder VAD CASB393WP CASB393WP (Open Class, Weatherproof) FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 15 Addressable 230V Relay I/O Unit CMIO353 CMIO353 Addressable 4-Way Sounder CSC354CPR CSC354CPR Controller Addressable Spur Isolator Unit CSI350 CSI350 Addressable Zone Monitor Unit CZMU352 CZMU352 Addressable Zone Monitor Unit CZMU352-IS CZMU352-IS (Intrinsically Safe) FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 16 10+ Panels c/w TCP/IP interlink Graphical Visualisation Software - Up to 2 Panels c/w EC0232 interface N/A EFGVS1-2 EFGVS1-2 Graphical Visualisation Software - EFGVS3-6 EFGVS3-6 Up to 6 Panels c/w EC0232 interface FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 17 Safety Power Supply (24V/4.5A) SPS-2453 SPS-2453 Addressable Control Panel Spare Parts Addressable Loop Splitter Unit ZPCB2222 ZPCB2222 Addressable Loop Mimic LED PCB ZPCB2252-MML ZPCB2252-MML (Master) Addressable Loop Mimic LED PCB ZPCB2252-MSL ZPCB2252-MSL (Slave) FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 18 The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the control panel . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 19: Compatible Callpoints

    . All sounders have multiple selectable volume settings, the volume setting is controlled by the panel and so can be altered without needing to access the sounder . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 20: Base Sounder

    The FXN538 has been designed specifically to complement the latest generation of Eaton Fire Systems soft addressed detectors . It consists of a first fix bracket, and a main body which clips onto the bracket incorporating the sounder and a detector mounting base in a single composite assembly .
  • Page 21: Visual Alarm Devices (Vads)

    A loop powered flashing beacon is available for applications where visual alarm indication is required such as areas of high ambient noise or buildings which are used by people who are hard of hearing . CAB382 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 22: Dedicated Stand Alone Sounders

    . Two different versions are available standard version and an IP66 rated version . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 23: Interfaces

    I/O’s), this means that text information can be allocated to each channel . It also allows each individual input and output to be disabled (by address) . The maximum number of addressable CIO351SST per loop is 3 . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 24: Channel I/O Device With Mains Rated Switching

    The input is suitable for use as a fire signal input such as from a sprinkler flow switch, however it can also be used to monitor non fire inputs such as an external keyswitch . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 25: Zone Monitor Units

    . In addition it has the facility to connect two circuits of conventional polarised sounders, which are monitored by means of an end of line resistor and powered in alarm conditions from FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 26 1 is required at the start of each spur . Please refer to BS5839 Pt1:2017 for details of the maximum allowable area to be covered by a single spur/zone . CSI350 CSC354CPR FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 27: Way Sounder Circuit Controller

    L .E .L (lower explosion limit) or PPM (parts per million) . This interface requires an external power supply . CGI420r This module is the same as the CGI420 but also comes with a relay output . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 28: Micro Interfaces

    400011FIre-0025X (MCoM-r) is a compact single channel output unit used to control or signal external equipment which require removal of power for reset purposes . This device is identified as an I/O device by a Eaton addressable panel . The maximum number of I/O devices per loop is 20 .
  • Page 29: Technical Input/Output Unit

    A specific resistance is must be placed in parallel to the end-of-line resistor to report the fan is in the active condition and removed to report the fan is in the inactive condition . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 30: Fan Controller Interfaces

    Compatible Equipment Fan controller interfaces (FC6, FC18) FC6 and FC18 Interface are designed to work with the Eaton range of analogue fire alarm control panels, providing the capability to control and display the status of AHU fans . FC6 and FC18 Interface is connected to a Eaton analogue addressable fire alarm...
  • Page 31: Equipment Compatibility

    Equipment compatibility Sensors Loop wired sensors must be of the Eaton Fire Systems soft addressed analogue type . Eaton Fire Systems conventional detectors can be connected via an CZMU352 interface . The connection of other detector types via an CZMU352 interface is not recommended .
  • Page 32: Relays/Auto-Dialers And Auxiliary Equipment

    Any modifications other than those stated in this manual, or any other use of this product may cause interference and it is the responsibility of the user to comply with the EMC and Low Voltage Directives . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 33: System Overview

    . For initial configuration or major system changes special PC configuration software is available enabling Eaton Service personnel to do this more efficiently than can be achieved using the system screen . Existing configurations can be uploaded to the PC so that changes can be made to the existing system rather than having to revert to initial files .
  • Page 34: Spur Tolerant Soft Addressing

    . Similarly if a device is removed, the relevant address is saved as a spare address for future use, the addresses of the remaining devices are not altered . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 35: Integral Power Supply And Battery

    A single concealed locking mechanism provides access to both the printer door and the display cover . Additional buttons are provided to scroll the display and to silence the fault buzzer without opening the lockable cover . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 36: Technical Specification

    1.0amp Float Voltage 27.4 Volts Final Voltage 21.0Volts Constant voltage with 0.970A Charging characteristics limit with temperature compensation Maximum current drawn from the batteries when the 3.5Amps mains is not available FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 37: Inputs

    End of line resistor Fire protecting equipment Max Load 60 ma Fused (PTC3) 100mA polyswitch End of Line resistor Fault routing equipment Max Load 30 ma Fused (PTC1) 100mA polyswitch End of Line resistor FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 38: Auxiliary Relays

    Printer (Optional) Type High speed thermal Number of characters per Line Type of paper 58mm x 46mm Thermal Roll Replacement paper roll order code ADF6PRINTERPAPER FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 39: Mechanical Specification

    Material used Poly Carbonate Flammability rating UL 94 5VA CAutIon risk of explosion if battery is replaced by an incorrect type dispose of the used batteries according to the instructions . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 40: Optional Functions As Per En54 P2&4

    . Ensure the polarity of the connections is observed at all times and end of line resistors ( 6K8 5% ) are fitted for correct operation . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 41: Output To Fault Warning Routing Equipment

    This is abbreviated in the touch screen by “AC” and it is displayed in the fire window at access level 2 .This counter can only be reset by the manufacturer . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 42: Optional Auxiliary Board Vds Requirement

    Fire Alarm Brigade Panel Output 6: Disablement of Sounders • This output is ON to indicate that the sounders have been disabled either by the control and indicating equipment or the Fire Brigade Panel. FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 43 End Of Line resistor 3K3 • 680 Ohm across input to actiavte input • relay outputs Normal status-> input sees a 3K3 resistor • Active status-> input sees a 680 ohm resistor • FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 44: Optional Functions Not Approved To En54 P2&4

    Commission per loop (option not required by en54 pt2) This mode is programmed at access level 3 . This allows the commissioning engineer to auto learn one loop at the time FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 45 . timer t1/t2 with Call point override (option not required by en54 pt2) This is similar to the above except a call point alarm will activate the output instantly . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 46: Cable & Wiring

    7. Loop feeds and returns should NEVER be used within the same cable Cable resistance Core diameter Typical FP200 resistance 1.0mm² 18.1 Ohms/km/Core 1.5mm² 12.1 Ohms/km/Core 2.5mm² 7.41 Ohms/km/Core 4.0mm² 4.61 Ohms/km/Core FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 47 . Secure the cable to the side of the box using the cable clip provided . ote: The mains cable tail ends must be insulated to prevent dangerous conditions arising in the event of accidental switching on of the mains supply . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 48: Installation

    . Temperatures in excess of 40°C and below 5°C should be avoided, if in doubt consult Eaton Service . The panel should be located away from any potential hazard, in a position where it is readily accessible to authorised staff, and the fire services, ideally on the perimeter of a building near a permanent entrance .
  • Page 49: Fixing Details

    Installing Cabling Once the backbox is mounted the next stage is to install the power and loop cables and fit the glands . 479mm 400mm 227mm 364mm 309mm 117mm 472mm 132mm FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 50: External Connections (Mains Supply)

    Wiring configurations Spurs can be taken off the loop in the following ways: 1. CZMU352 Addressable Interface - Allows up to 20 conventional smoke detectors and unlimited Eaton conventinal call points FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 51: Networking

    . The cable screen should be connected to the earth of one panel in each building . Network cable Network card (Panel 1) Network card (Panel 2) FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 52: Input/Outputs

    4 sounder circuits . WArnInG All sounders must be polarised Both sounder circuits must be terminated with a 6800 Ohm end of line resistor do not eXCeed tHe rAted outPut Current FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 53: Output Fire Alarm Routing Equipment

    . Please ensure that all equipments connected to this output will only draw current when a fire condition exists . WArnInG do not eXCeed tHe rAted outPut Current FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 54: Maintenance

    . e .g . high pressure air spray . Every 5 years Replace sealed lead acid battery . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 55: Servicing

    Maintenance Servicing Eaton Service can offer a regular servicing contract . Further copies of this log book are obtainable from:- eaton electrical systems ltd . Wheatley Hall road doncaster united Kingdom dn2 4nB tel: +44 (0) 1302 303303 Fax: +44 (0) 1302 367155 Cleaning When cleaning the panel, use a moist cloth .
  • Page 56: Panel Assembly Information

    The door is designed as a drop on fit . Offer the door up to the back box in the open position as shown below . Align the hinges and lower the door onto the hinge pins . Check the hinges are secure . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 57: Installing A Hinged Cover

    Insert the bottom peg of the hinged cover into the panel as shown and close the hinged cover followed by the printer door . Next from the back of the panel insert second peg though the hole shown below and push into the hinged cover . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 58: Fitting Printer Paper Roll

    New paper roll simply drops into the holder. Push paper underneath the roller as shown until printer automatically loads the paper. Tear off excess paper and close the printer compartment door. FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 59: Commissioning The Control Panel System

    . This facility can be accessed via the engineering menu and can be switched on or off at any time as required . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 60: Up/Downloading Using Pc Software

    The PC is connected to each Panel on the network in turn . All data for the Panel is downloaded . For networked systems, panels are identified by panel number, P1, P2 etc . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 61: Panel Fault Finding

    = -0.6 Mon +28V re (Depends on programming) See scope plot for monitoring condition = -0.6 Mon +28V re (Depends on programming) = -0.6 Mon +28V re (Depends on programming) Static conditions (No data) = 0V (No data) FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 62: Pc Commissioning Software

    . Panel does not go to Fire, trigger is non-latching Isolate Zones = This allows a group of zones (max 8) to be isolated from the • trigger . Panel does not go to Fire, trigger is non-latching FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 63: Non-Latching

    User can define between zones or addresses to be isolated on activation of the device . The isolate list button enables the user to enter upto 8 unique zones or addresses . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 64: Sounder Trigger

    . Allocation List If the sounder trigger is by address, zone or panel, then the trigger source can be selected from the Allocation List box .Panel outputs FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 65: Dependency Detection

    . When the ‘Dependency’ box is checked - the ‘Allocate device’ button allows the user to populate this list . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 66: Panel Controls & Indicators

    Monitors status of FRE output Check with system supervisor Extinguisher ⑩ Display activation of extinguishers (if option fitted) Check with system supervisor activated ⑪ Delay active Delays on outputs active Check with system supervisor FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 67 Panel controls & indicators Insert supervisor key here Log book storage Printer Paper roll storage Insert supervisor key here Optional hinged cover Scroll up Mute buzzer Scroll down FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 68: Touch Screen Display

    . When displaying the system menu on the touch screen, the last 5 lines of the display are shown in reverse text . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 69: Panel Operation

    Meeting Room 1, Building 1, 1st floor First Fire Loop: 1, Zone: 2, Type: Optical (150) System Healthy 10 Zones Active Print All Help Total Fires= 1 Tuesday dd-mm-yyyy Tuesday Dd-mmm-yyy 16:25.25 16:25.25 BST On BST On FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 70: Public Access Level 1

    Lp: 1, Ad: 4, Z: 1, Opto/thermal [69] 005 12:35:59 Fault! : Device5 005 03-Jun-03 12:51 Warning! : Device5 Lp: 1, Ad: 4, Z: 1, Opto/thermal [69] Lp: 1, Ad: 5, Z: 1, Opto/thermal [69] FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 71: Evacuate (Access Level 2)

    View View Fires Faults This will silence ALL sounders View Pre AC = 0 View Do you wish to continue? Alarms Disabled Zone: 0 Addresses: 0 Touch button to View list FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 72: Mute Buzzer

    View Do you wish to continue? Disabled Faults 001 14:22:49 Mains Failure Faults = Short circuits, broken detectors etc. To remove faults from this list: 1) Fix Fault 2) Reset Panel FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 73: Pre-Alarms

    Silence Mute Reset Evacuate FRE Off Alarms Buzzer Fires Others AC = 0 Disabled Alarms Faults Pre-alarm = Some smoke /heat but below fire threshold These warnings will appear and disappear FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 74: Disabled Devices

    Buzzer View Fires View Pre AC=100 View Alarms View Disabled Others Faults Enable/Disable Weekly Test Send Log to PC Print View Log Check Config. Lamp Test Send analogue values to PC FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 75 Touch “Disabled”button to Enable Enable all Devices? Zone 001 Zone 1 Enabled Do you want to continue? Zone 002 Zone 2 Disabled Zone 003 Zone 3 Disabled Zone 004 Zone 4 Enabled FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 76: Print

    Lamp Test View Fires View Pre AC = 19 LED’s will light in Alarms View numerical order View Disabled Faults Others Cancel Enable/Disable Weekly Test Print View Log Lamp Test Check Config. FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 77: Weekly Test

    * Features outside EN54 Spec Awaiting Alarm Signal Weekly test Do you want to continue? Cancel The weekly test will ask the user to carry out a reset on completion of the callpoint operation . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 78: Viewing Events

    . Once the maximum 10,000 events has been reached, the panel will automatically overwrite the oldest event every time a new event is stored . The event log can only be reset by an approved service engineer . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 79: Check Auto Config

    Replace Device Exit Supervisor Supervisor Silence Mute Press the Reset Evacuate FRE Off FRE Off Alarms Buzzer supervisor mode button at the top left of Print Exit the screen. Check Auto Config FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 80: Replace Device

    Change Device Auto Config. Supervisor FRE Off Check Auto Config Replace Device Exit Supervisor Supervisor FRE Off FRE Off Enter Loop 1 Address Select a Loop Loop 1 Loop 2 Exit Exit FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 81: Test Device (Access Level 3)

    Loop: 1, Zone: 2, Type: Optical 003 Storage/archive, Building 1, 1st floor Loop: 1, Zone: 2, Type: Optical 004 Meeting Room 1, Building 1, 1st floor Loop: 1, Zone: 2, Type: Optical FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 82: Test Zone

    Do you want to continue? 15 seconds on, 30 seconds off Sound Level Test Mode Touch “Stop” button to stop test Do you want to continue? Stop FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com Sound Level Test Mode...
  • Page 83: Global Flashing Led On/Off

    Exit Reset Buzzer FRE Off from the test menu screen. ” Test Device Test Zone Sound Level Test Mode One Man Walk Test Global Flashing LED On/Off Global flashing LED’s Flashing FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 84: One Man Walk Test

    One Man Walk Test Global Flashing LED On/Off * Feature is outside EN54 spec One Man Walk Test One Man Walk Test Do you want to continue? Awaiting Alarm Signal Stop FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 85: Commission

    . IMPORTANT: Load CDR from Laptop Do not click commission before pressing “Yes” on the This will erase the current CDR “Load CDR” screen . Do you want to continue? FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 86: Download Cdr From Laptop

    Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Download CDR to Laptop Start PC program Press "OK" to continue or "Cancel" to exit Cancel FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 87: Auto Learn

    Yes - autolearn loop 1 only Pre-addressed auto-learn Yes - autolearn loop 2 only Yes - autolearn loop 3 only Maintenance auto-learn Yes - autolearn loop 4 only Yes - autolearn all loops FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 88: Erase Log

    Number of Panels Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) This will delete all log entries Do you want to continue FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 89: System Details

    Exit Reset FRE off Loop 1 Loop 2 Loop 3 Loop 4 Voice Annunciator Repeater ZMU/{SUM Beam Detector Technical Timer Access Control Emerg.Light.Module Carbon Monoxide Page 1 Page 2 Page 3 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 90: Analogue Level

    Alarm >= View View Disabled Panel PreAlarm Faults Others Loop Fault <= Enable/Disable Weekly Test Send Log to PC Print View Log Check Config. Lamp Test Send analogue values to PC FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 91: Printer Settings

    Change Panel Number Number of Panels Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Service Reset Exit FRE off Auto Request FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 92: Change Panel Number

    Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Change Panel Number ......4 5 6 7 8 9 ok 0 Cancel FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 93: Number Of Panels In Network

    Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Number of Panels in Network ......4 5 6 7 8 9 ok 0 Cancel FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 94: Screen Cover

    Change Panel Number Number of Panels Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Service Exit Reset FRE off Installed Not Required FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 95: Programming I/O And Sounders

    Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Reset Exit FRE off Sound Settings T1/T2 Auxillary Board Alarm Verification Feature FRE impedance band FRE double-knock Override Sounder tone FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 96: Sound Settings

    This will effect all sounders Volume Medium High Sound Service Service Exit Reset Exit Reset FRE off FRE off Sound This will effect all sounders Volume Slow Woop Two Tone Sound Continuous FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 97: Change Date/Time

    2. Set the Time Using the Buttons Shown Below. Service Cancel Reset FRE Off Current Time: Hour Mins Mins 10:16:12 Hour Mins Mins BST On Current Date: Year Month Wednesday Month Year dd-mmm-yyyy FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 98: Change Text

    Loop: 1, Zone: 1, Type : Opto/thermal 004 Device 4, Zone 1 Loop: 1, Zone: 1, Type : Opto/thermal CAPS 005 Device 5, Zone 1 SPACE CANCEL OTHER Loop: 1, Zone: 1, Type : Opto/thermal FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 99: Change Zone Text

    FRE Off Enter the name for Zone 2 Exit Zone 2 ..................Zone 001 Zone 1 Zone 002 Zone 2 Zone 003 Zone 3 Zone 004 Zone 4 CAPS SPACE CANCEL OTHER FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 100: Change Panel Text

    Italian Mode Network Protocol 2. Press “Change Panel Text” Service Exit Reset FRE Off Correct Panel Text Change address text DF6000 ..................Change zone text Change Panel Text CAPS SPACE CANCEL OTHER FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 101: Configure Zones

    Touch the dash to 004 Device 4, Zone 2 move the device into Loop: 1, Zone: 2, Type : Opto/thermal the selected zone. 005 Device 5, Zone2 Loop: 1, Zone: 2, Type : Opto/thermal FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 102: Change User Code

    ......7 8 9 Verify New Code: Change User code ......ok 0 Cancel Passcode is not correct. Verification is incorrect New Password accepted No change made No change made Saved FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 103: Add Zone

    Configure Heat Detectors Change Text Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE Off Add Zone Delete Zone Add Device Delete Device Add Zone ? FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 104: Delete Zone

    FRE Off Exit Touch row to delete Zone 001 Zone 1 Zone 002 Zone 2 Zone 003 Zone 3 Zone 004 Zone 4 3. Confirm or Cancel Deletion Delete Zone 2? FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 105: Add Device

    Loop 1 Loop 2 Loop 3 Loop 4 Exit 3. Confirm New Device and Loop Loop 2 Loop 2 Saving... Scanning Loop Loop 1, Address 30, Type [device type] Exit Exit FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 106: Delete Device

    005 Device 5, Zone 1 Loop: 1, Zone: 1, Type : Opto/thermal 3. Confirm or Cancel Deletion Delete Device 3? Device 3 Loop 1, Address 3, Device Type Opto/thermal Yes, but keep settings FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 107: Configure Heat Detectors

    Loop: 1, Zone: 2, Type : Opto/thermal 005 Device 5, Zone 1 Loop: 1, Zone: 1, Type : Opto/thermal 3. Select appropriate detector class. Service Reset FRE Off Thermal A1R Thermal BS Thermal CS Exit FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 108: Network

    Pre-Alarm Password protection The Eaton Fire Systems control panel system has password protection which restricts access to the DISABLE Menu and to TEST/COMMISSIONING MODE . The password is a four digit code and the default number is 2214 . The password entry screen is accessed via the supervisor mode button .
  • Page 109: Appendix

    Appendix Appendix System wiring FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 110: Detector Base Wiring (Fxn720)

    E E a a r r t t h h s s c c r r e e e e n n o o f f c c a a b b l l e e t t o o b b e e c c o o n n t t i i n n u u o o u u s s b b e e t t w w e e e e n n s s e e n n s s o o r r s s FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 111: Call Point Wiring (Fxn501/Fxn503)

    Two tone 610 / 910Hz @ 1Hz cycle Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap S S + + F F + + Due to restricted access space, do not use excessive cable in this area. FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 112: Loop Powered Beacon Wiring (Cab382)

    . earth screen must be continuous along entire length of loop . Analogue Addressable Loop ote: Care should be taken to ensure the cable does not put stress on the circuit board FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 113: Ip66 Wall Sounder Wiring (Fxn538Lpswp, Fxn539Lpswp)

    A A n n a a l l o o g g u u e e A A d d d d r r e e s s s s a a b b l l e e L L o o o o p p FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 114: Base Sounder Vad (Casbb394)

    Base terminal 1, 2, 3 and 4 not used . All wiring terminates as shown above . WArnInG do not use high voltage testers if AnY equipment is connected to the system . earth screen must be continuous along entire length of loop . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 115: Wall Sounder Vad (Casb393)

    2 . Soft addressed . standard connections WArnInG do not use high voltage testers if AnY equipment is connected to the system . earth screen must be continuous along entire length of loop . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 116: Ip66 Wall Sounder Vad (Casb393Wp)

    2 . Soft addressed . standard connections WArnInG do not use high voltage testers if AnY equipment is connected to the system . earth screen must be continuous along entire length of loop . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 117: Way Input Output Unit (Cio351, Cio351S, Cio351Sst)

    2 . The end of line resistor must always be fitted, even if the inputs are unused 3 . Monitored inputs can detect open or short circuit faults 4 . Output relays are volt-free contacts and are not monitored FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 118: Channel Mains Rated I/O Unit Wiring (Cmio353)

    I I N N P P U U T T ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistor must always be fitted, even if the spur is unused FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 119: Zone Monitor Unit Wiring (Czmu352)

    5 . Maximum number of call points allowed is unlimited 6 . Detector zone end of line device is EOLM-1 (supplied) 7 . Callpoint zone has end of line resistor FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 120: Intrinsically Safe Zone Monitor Unit Wiring (Czmu352-Is)

    3 . Only connect cable screen to its adjacent earth terminal 4 . The end of line resistor must always be fitted, even if the spur is unused 5 . Maximum spur length – See BS5839 Pt1:2001 for Zone Coverage FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 121: Shop Monitor Unit Wiring (Msu840)

    4 . Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage 5 . Maximum number of call points allowed is unlimited 6 . Detector zone end of line device is EOLM-1 7 . Callpoint zone has end of line resistor FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 122: Spur Isolator Wiring (Csi350)

    1 . Only connect cable screen to its adjacent earth terminal 2 . For maximum spur length / load see BS5839 Pt1:2002 3 . This unit can only be used with Eaton CAB300 and CDB300/I Sensor bases and compatible sensors...
  • Page 123: Way Sounder Controller Wiring (Csc354Cpr)

    B B A A T T T T E E R R Y Y ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistors must always be fitted, even if the sounder circuits are unused FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 124: 4-20Ma Interface Wiring (Cgi420, Cit420, Cgi420R, Cit420R)

    Recommended Loop Cable Type: FIRETUF , FP200, MICC No addressing of the interface is required . See control panel operation for details . There are no serviceable parts so no maintenance procedures apply FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 125: Micro Zone Monitor Module Wiring (Jiu872)

    JIU872 standard connections ote: 1 . This unit can only be used with Eaton FXN520 detector base and compatible detectors 2 . Only connect cable screen to its adjacent earth terminal 3 . The end of line resistor must always be fitted, even if the spur is unused 4 .
  • Page 126: Micro Input Module Wiring (Mjim)

    1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistor provided must always be fitted, even if the input is unused 3 . Monitored inputs can detect open or short circuit faults FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 127: Micro Output Module Wiring (Mjom, Mjom-R, Mjom-S, Mjom-Fc)

    EARTH Earth Loop Out+ Loop Out- MJOM Earth ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . Output relay are volt-free contacts and are not monitored FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 128: Typical Smoke Management Topology Diagram

    Appendix Typical smoke management topology diagram Grouped smoke management devices FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 129: En54 Spec Label Positioning

    Special Waste Regulation 1996 . It is recommended that the following authorities are contacted before any attempt is made to dispose of batteries; Environment Agency Local office, Local Authority Environmental Health or Waste Handling department . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 130: Ce Marking

    Test condition Other technical data: see Doc. 25-14683 held by the manufacturer 2831 doP0227 Assessed to ISO 9001:2008 Certification number 714w/01 Approved to EN54-2 1997 & A1;2006 EN54-4:1997 & A1;2002 A2:2006 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
  • Page 131: Notes

    Notes Notes FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...