Page 8
THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES . In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental...
Page 9
That is why we offer you so many ways to get the support you need . Whether it is by phone, fax, or email, you can access Eaton’s support information 24 hours a day, seven days a week . Our wide range of services is listed below . You should contact your local distributor for product pricing, availability, ordering, expediting and repairs .
Page 10
IF BAtterY Is rePlACed BY An InCorreCt tYPe dIsPose oF tHe used BAtterIes ACCordInG to tHe InstruCtIons (Appendix page 129) . this product must only be disposed of in accordance with the Weee directive . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Introduction Introduction FX6000 provides all of the sophisticated features required of a leading edge analogue addressable fire system along with the simple operation and neat installation demanded by installers and building users . The panel can be flush or surface mounted and the generously sized metal back box allows ample facilities for rear or top cable entries .
5. Final commissioning A minimum of two weeks notice is required from receipt of Address Schedule and Commissioning request form for a Eaton Service Engineer to attend site and implement/oversee the final commissioning procedures (see Commissioning section), in conjunction with the installer .
Page 15
Addressable 230V Relay I/O Unit CMIO353 CMIO353 Addressable 4-Way Sounder CSC354CPR CSC354CPR Controller Addressable Spur Isolator Unit CSI350 CSI350 Addressable Zone Monitor Unit CZMU352 CZMU352 Addressable Zone Monitor Unit CZMU352-IS CZMU352-IS (Intrinsically Safe) FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Page 16
10+ Panels c/w TCP/IP interlink Graphical Visualisation Software - Up to 2 Panels c/w EC0232 interface N/A EFGVS1-2 EFGVS1-2 Graphical Visualisation Software - EFGVS3-6 EFGVS3-6 Up to 6 Panels c/w EC0232 interface FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Page 17
Safety Power Supply (24V/4.5A) SPS-2453 SPS-2453 Addressable Control Panel Spare Parts Addressable Loop Splitter Unit ZPCB2222 ZPCB2222 Addressable Loop Mimic LED PCB ZPCB2252-MML ZPCB2252-MML (Master) Addressable Loop Mimic LED PCB ZPCB2252-MSL ZPCB2252-MSL (Slave) FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Page 18
The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the control panel . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. All sounders have multiple selectable volume settings, the volume setting is controlled by the panel and so can be altered without needing to access the sounder . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
The FXN538 has been designed specifically to complement the latest generation of Eaton Fire Systems soft addressed detectors . It consists of a first fix bracket, and a main body which clips onto the bracket incorporating the sounder and a detector mounting base in a single composite assembly .
A loop powered flashing beacon is available for applications where visual alarm indication is required such as areas of high ambient noise or buildings which are used by people who are hard of hearing . CAB382 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. Two different versions are available standard version and an IP66 rated version . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
I/O’s), this means that text information can be allocated to each channel . It also allows each individual input and output to be disabled (by address) . The maximum number of addressable CIO351SST per loop is 3 . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
The input is suitable for use as a fire signal input such as from a sprinkler flow switch, however it can also be used to monitor non fire inputs such as an external keyswitch . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. In addition it has the facility to connect two circuits of conventional polarised sounders, which are monitored by means of an end of line resistor and powered in alarm conditions from FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Page 26
1 is required at the start of each spur . Please refer to BS5839 Pt1:2017 for details of the maximum allowable area to be covered by a single spur/zone . CSI350 CSC354CPR FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
L .E .L (lower explosion limit) or PPM (parts per million) . This interface requires an external power supply . CGI420r This module is the same as the CGI420 but also comes with a relay output . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
400011FIre-0025X (MCoM-r) is a compact single channel output unit used to control or signal external equipment which require removal of power for reset purposes . This device is identified as an I/O device by a Eaton addressable panel . The maximum number of I/O devices per loop is 20 .
A specific resistance is must be placed in parallel to the end-of-line resistor to report the fan is in the active condition and removed to report the fan is in the inactive condition . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Compatible Equipment Fan controller interfaces (FC6, FC18) FC6 and FC18 Interface are designed to work with the Eaton range of analogue fire alarm control panels, providing the capability to control and display the status of AHU fans . FC6 and FC18 Interface is connected to a Eaton analogue addressable fire alarm...
Equipment compatibility Sensors Loop wired sensors must be of the Eaton Fire Systems soft addressed analogue type . Eaton Fire Systems conventional detectors can be connected via an CZMU352 interface . The connection of other detector types via an CZMU352 interface is not recommended .
Any modifications other than those stated in this manual, or any other use of this product may cause interference and it is the responsibility of the user to comply with the EMC and Low Voltage Directives . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. For initial configuration or major system changes special PC configuration software is available enabling Eaton Service personnel to do this more efficiently than can be achieved using the system screen . Existing configurations can be uploaded to the PC so that changes can be made to the existing system rather than having to revert to initial files .
. Similarly if a device is removed, the relevant address is saved as a spare address for future use, the addresses of the remaining devices are not altered . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
A single concealed locking mechanism provides access to both the printer door and the display cover . Additional buttons are provided to scroll the display and to silence the fault buzzer without opening the lockable cover . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
1.0amp Float Voltage 27.4 Volts Final Voltage 21.0Volts Constant voltage with 0.970A Charging characteristics limit with temperature compensation Maximum current drawn from the batteries when the 3.5Amps mains is not available FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
End of line resistor Fire protecting equipment Max Load 60 ma Fused (PTC3) 100mA polyswitch End of Line resistor Fault routing equipment Max Load 30 ma Fused (PTC1) 100mA polyswitch End of Line resistor FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Printer (Optional) Type High speed thermal Number of characters per Line Type of paper 58mm x 46mm Thermal Roll Replacement paper roll order code ADF6PRINTERPAPER FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Material used Poly Carbonate Flammability rating UL 94 5VA CAutIon risk of explosion if battery is replaced by an incorrect type dispose of the used batteries according to the instructions . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. Ensure the polarity of the connections is observed at all times and end of line resistors ( 6K8 5% ) are fitted for correct operation . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
This is abbreviated in the touch screen by “AC” and it is displayed in the fire window at access level 2 .This counter can only be reset by the manufacturer . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Fire Alarm Brigade Panel Output 6: Disablement of Sounders • This output is ON to indicate that the sounders have been disabled either by the control and indicating equipment or the Fire Brigade Panel. FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Page 43
End Of Line resistor 3K3 • 680 Ohm across input to actiavte input • relay outputs Normal status-> input sees a 3K3 resistor • Active status-> input sees a 680 ohm resistor • FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Commission per loop (option not required by en54 pt2) This mode is programmed at access level 3 . This allows the commissioning engineer to auto learn one loop at the time FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Page 45
. timer t1/t2 with Call point override (option not required by en54 pt2) This is similar to the above except a call point alarm will activate the output instantly . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
7. Loop feeds and returns should NEVER be used within the same cable Cable resistance Core diameter Typical FP200 resistance 1.0mm² 18.1 Ohms/km/Core 1.5mm² 12.1 Ohms/km/Core 2.5mm² 7.41 Ohms/km/Core 4.0mm² 4.61 Ohms/km/Core FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Page 47
. Secure the cable to the side of the box using the cable clip provided . ote: The mains cable tail ends must be insulated to prevent dangerous conditions arising in the event of accidental switching on of the mains supply . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. Temperatures in excess of 40°C and below 5°C should be avoided, if in doubt consult Eaton Service . The panel should be located away from any potential hazard, in a position where it is readily accessible to authorised staff, and the fire services, ideally on the perimeter of a building near a permanent entrance .
Installing Cabling Once the backbox is mounted the next stage is to install the power and loop cables and fit the glands . 479mm 400mm 227mm 364mm 309mm 117mm 472mm 132mm FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Wiring configurations Spurs can be taken off the loop in the following ways: 1. CZMU352 Addressable Interface - Allows up to 20 conventional smoke detectors and unlimited Eaton conventinal call points FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. The cable screen should be connected to the earth of one panel in each building . Network cable Network card (Panel 1) Network card (Panel 2) FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
4 sounder circuits . WArnInG All sounders must be polarised Both sounder circuits must be terminated with a 6800 Ohm end of line resistor do not eXCeed tHe rAted outPut Current FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. Please ensure that all equipments connected to this output will only draw current when a fire condition exists . WArnInG do not eXCeed tHe rAted outPut Current FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. e .g . high pressure air spray . Every 5 years Replace sealed lead acid battery . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Maintenance Servicing Eaton Service can offer a regular servicing contract . Further copies of this log book are obtainable from:- eaton electrical systems ltd . Wheatley Hall road doncaster united Kingdom dn2 4nB tel: +44 (0) 1302 303303 Fax: +44 (0) 1302 367155 Cleaning When cleaning the panel, use a moist cloth .
The door is designed as a drop on fit . Offer the door up to the back box in the open position as shown below . Align the hinges and lower the door onto the hinge pins . Check the hinges are secure . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Insert the bottom peg of the hinged cover into the panel as shown and close the hinged cover followed by the printer door . Next from the back of the panel insert second peg though the hole shown below and push into the hinged cover . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
New paper roll simply drops into the holder. Push paper underneath the roller as shown until printer automatically loads the paper. Tear off excess paper and close the printer compartment door. FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. This facility can be accessed via the engineering menu and can be switched on or off at any time as required . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
The PC is connected to each Panel on the network in turn . All data for the Panel is downloaded . For networked systems, panels are identified by panel number, P1, P2 etc . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
= -0.6 Mon +28V re (Depends on programming) See scope plot for monitoring condition = -0.6 Mon +28V re (Depends on programming) = -0.6 Mon +28V re (Depends on programming) Static conditions (No data) = 0V (No data) FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. Panel does not go to Fire, trigger is non-latching Isolate Zones = This allows a group of zones (max 8) to be isolated from the • trigger . Panel does not go to Fire, trigger is non-latching FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
User can define between zones or addresses to be isolated on activation of the device . The isolate list button enables the user to enter upto 8 unique zones or addresses . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. Allocation List If the sounder trigger is by address, zone or panel, then the trigger source can be selected from the Allocation List box .Panel outputs FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. When the ‘Dependency’ box is checked - the ‘Allocate device’ button allows the user to populate this list . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Monitors status of FRE output Check with system supervisor Extinguisher ⑩ Display activation of extinguishers (if option fitted) Check with system supervisor activated ⑪ Delay active Delays on outputs active Check with system supervisor FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Page 67
Panel controls & indicators Insert supervisor key here Log book storage Printer Paper roll storage Insert supervisor key here Optional hinged cover Scroll up Mute buzzer Scroll down FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. When displaying the system menu on the touch screen, the last 5 lines of the display are shown in reverse text . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Meeting Room 1, Building 1, 1st floor First Fire Loop: 1, Zone: 2, Type: Optical (150) System Healthy 10 Zones Active Print All Help Total Fires= 1 Tuesday dd-mm-yyyy Tuesday Dd-mmm-yyy 16:25.25 16:25.25 BST On BST On FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
View View Fires Faults This will silence ALL sounders View Pre AC = 0 View Do you wish to continue? Alarms Disabled Zone: 0 Addresses: 0 Touch button to View list FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
View Do you wish to continue? Disabled Faults 001 14:22:49 Mains Failure Faults = Short circuits, broken detectors etc. To remove faults from this list: 1) Fix Fault 2) Reset Panel FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Silence Mute Reset Evacuate FRE Off Alarms Buzzer Fires Others AC = 0 Disabled Alarms Faults Pre-alarm = Some smoke /heat but below fire threshold These warnings will appear and disappear FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Buzzer View Fires View Pre AC=100 View Alarms View Disabled Others Faults Enable/Disable Weekly Test Send Log to PC Print View Log Check Config. Lamp Test Send analogue values to PC FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Page 75
Touch “Disabled”button to Enable Enable all Devices? Zone 001 Zone 1 Enabled Do you want to continue? Zone 002 Zone 2 Disabled Zone 003 Zone 3 Disabled Zone 004 Zone 4 Enabled FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Lamp Test View Fires View Pre AC = 19 LED’s will light in Alarms View numerical order View Disabled Faults Others Cancel Enable/Disable Weekly Test Print View Log Lamp Test Check Config. FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
* Features outside EN54 Spec Awaiting Alarm Signal Weekly test Do you want to continue? Cancel The weekly test will ask the user to carry out a reset on completion of the callpoint operation . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. Once the maximum 10,000 events has been reached, the panel will automatically overwrite the oldest event every time a new event is stored . The event log can only be reset by an approved service engineer . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Replace Device Exit Supervisor Supervisor Silence Mute Press the Reset Evacuate FRE Off FRE Off Alarms Buzzer supervisor mode button at the top left of Print Exit the screen. Check Auto Config FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Change Device Auto Config. Supervisor FRE Off Check Auto Config Replace Device Exit Supervisor Supervisor FRE Off FRE Off Enter Loop 1 Address Select a Loop Loop 1 Loop 2 Exit Exit FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Do you want to continue? 15 seconds on, 30 seconds off Sound Level Test Mode Touch “Stop” button to stop test Do you want to continue? Stop FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com Sound Level Test Mode...
Exit Reset Buzzer FRE Off from the test menu screen. ” Test Device Test Zone Sound Level Test Mode One Man Walk Test Global Flashing LED On/Off Global flashing LED’s Flashing FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
One Man Walk Test Global Flashing LED On/Off * Feature is outside EN54 spec One Man Walk Test One Man Walk Test Do you want to continue? Awaiting Alarm Signal Stop FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. IMPORTANT: Load CDR from Laptop Do not click commission before pressing “Yes” on the This will erase the current CDR “Load CDR” screen . Do you want to continue? FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Download CDR to Laptop Start PC program Press "OK" to continue or "Cancel" to exit Cancel FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Number of Panels Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) This will delete all log entries Do you want to continue FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Alarm >= View View Disabled Panel PreAlarm Faults Others Loop Fault <= Enable/Disable Weekly Test Send Log to PC Print View Log Check Config. Lamp Test Send analogue values to PC FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Change Panel Number Number of Panels Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Service Reset Exit FRE off Auto Request FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Change Panel Number ......4 5 6 7 8 9 ok 0 Cancel FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Number of Panels in Network ......4 5 6 7 8 9 ok 0 Cancel FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Change Panel Number Number of Panels Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Service Exit Reset FRE off Installed Not Required FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Reset Exit FRE off Sound Settings T1/T2 Auxillary Board Alarm Verification Feature FRE impedance band FRE double-knock Override Sounder tone FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
This will effect all sounders Volume Medium High Sound Service Service Exit Reset Exit Reset FRE off FRE off Sound This will effect all sounders Volume Slow Woop Two Tone Sound Continuous FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
2. Set the Time Using the Buttons Shown Below. Service Cancel Reset FRE Off Current Time: Hour Mins Mins 10:16:12 Hour Mins Mins BST On Current Date: Year Month Wednesday Month Year dd-mmm-yyyy FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Loop: 1, Zone: 1, Type : Opto/thermal 004 Device 4, Zone 1 Loop: 1, Zone: 1, Type : Opto/thermal CAPS 005 Device 5, Zone 1 SPACE CANCEL OTHER Loop: 1, Zone: 1, Type : Opto/thermal FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
FRE Off Enter the name for Zone 2 Exit Zone 2 ..................Zone 001 Zone 1 Zone 002 Zone 2 Zone 003 Zone 3 Zone 004 Zone 4 CAPS SPACE CANCEL OTHER FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Italian Mode Network Protocol 2. Press “Change Panel Text” Service Exit Reset FRE Off Correct Panel Text Change address text DF6000 ..................Change zone text Change Panel Text CAPS SPACE CANCEL OTHER FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Touch the dash to 004 Device 4, Zone 2 move the device into Loop: 1, Zone: 2, Type : Opto/thermal the selected zone. 005 Device 5, Zone2 Loop: 1, Zone: 2, Type : Opto/thermal FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
......7 8 9 Verify New Code: Change User code ......ok 0 Cancel Passcode is not correct. Verification is incorrect New Password accepted No change made No change made Saved FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Configure Heat Detectors Change Text Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE Off Add Zone Delete Zone Add Device Delete Device Add Zone ? FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
FRE Off Exit Touch row to delete Zone 001 Zone 1 Zone 002 Zone 2 Zone 003 Zone 3 Zone 004 Zone 4 3. Confirm or Cancel Deletion Delete Zone 2? FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Pre-Alarm Password protection The Eaton Fire Systems control panel system has password protection which restricts access to the DISABLE Menu and to TEST/COMMISSIONING MODE . The password is a four digit code and the default number is 2214 . The password entry screen is accessed via the supervisor mode button .
E E a a r r t t h h s s c c r r e e e e n n o o f f c c a a b b l l e e t t o o b b e e c c o o n n t t i i n n u u o o u u s s b b e e t t w w e e e e n n s s e e n n s s o o r r s s FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Two tone 610 / 910Hz @ 1Hz cycle Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap S S + + F F + + Due to restricted access space, do not use excessive cable in this area. FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
. earth screen must be continuous along entire length of loop . Analogue Addressable Loop ote: Care should be taken to ensure the cable does not put stress on the circuit board FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
A A n n a a l l o o g g u u e e A A d d d d r r e e s s s s a a b b l l e e L L o o o o p p FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Base terminal 1, 2, 3 and 4 not used . All wiring terminates as shown above . WArnInG do not use high voltage testers if AnY equipment is connected to the system . earth screen must be continuous along entire length of loop . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
2 . Soft addressed . standard connections WArnInG do not use high voltage testers if AnY equipment is connected to the system . earth screen must be continuous along entire length of loop . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
2 . Soft addressed . standard connections WArnInG do not use high voltage testers if AnY equipment is connected to the system . earth screen must be continuous along entire length of loop . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
2 . The end of line resistor must always be fitted, even if the inputs are unused 3 . Monitored inputs can detect open or short circuit faults 4 . Output relays are volt-free contacts and are not monitored FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
I I N N P P U U T T ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistor must always be fitted, even if the spur is unused FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
5 . Maximum number of call points allowed is unlimited 6 . Detector zone end of line device is EOLM-1 (supplied) 7 . Callpoint zone has end of line resistor FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
3 . Only connect cable screen to its adjacent earth terminal 4 . The end of line resistor must always be fitted, even if the spur is unused 5 . Maximum spur length – See BS5839 Pt1:2001 for Zone Coverage FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
4 . Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage 5 . Maximum number of call points allowed is unlimited 6 . Detector zone end of line device is EOLM-1 7 . Callpoint zone has end of line resistor FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
1 . Only connect cable screen to its adjacent earth terminal 2 . For maximum spur length / load see BS5839 Pt1:2002 3 . This unit can only be used with Eaton CAB300 and CDB300/I Sensor bases and compatible sensors...
B B A A T T T T E E R R Y Y ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistors must always be fitted, even if the sounder circuits are unused FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Recommended Loop Cable Type: FIRETUF , FP200, MICC No addressing of the interface is required . See control panel operation for details . There are no serviceable parts so no maintenance procedures apply FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
JIU872 standard connections ote: 1 . This unit can only be used with Eaton FXN520 detector base and compatible detectors 2 . Only connect cable screen to its adjacent earth terminal 3 . The end of line resistor must always be fitted, even if the spur is unused 4 .
1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistor provided must always be fitted, even if the input is unused 3 . Monitored inputs can detect open or short circuit faults FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
EARTH Earth Loop Out+ Loop Out- MJOM Earth ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . Output relay are volt-free contacts and are not monitored FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Special Waste Regulation 1996 . It is recommended that the following authorities are contacted before any attempt is made to dispose of batteries; Environment Agency Local office, Local Authority Environmental Health or Waste Handling department . FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Test condition Other technical data: see Doc. 25-14683 held by the manufacturer 2831 doP0227 Assessed to ISO 9001:2008 Certification number 714w/01 Approved to EN54-2 1997 & A1;2006 EN54-4:1997 & A1;2002 A2:2006 FX6000 InstAllAtIon And oPerAtIon MAnuAl 25-14683-C December 2019 www.eaton.com...
Need help?
Do you have a question about the FX6000 and is the answer not in the manual?
Questions and answers