DEFINITION:
This fault is most likely due to intermi ent
low voltage control wiring connec ons.
Insure wiring is per the wiring diagram and
connec ons are secure and fully seated.
DIAGRAM #1
S8V2-SVX001-1A-EN
E17 Fault Code
Are serial motor
wires firmly connected
NO
to motor and IFC?
YES
Is 120 VAC measured at
the line voltage connector
at the motor? (5 pin
NO
connector terminals 4 and
5)
YES
Remove the serial
motor wiring
harness at the IFC.
Apply 24 VAC to
wires 3 & 4.
Does motor run?
NO
YES
Replace IFC. Check
opera on
#4 = WHITE wire, connects to TX
#3 = BLACK wire, connects to GND
T T r r o o u u b b l l e e s s h h o o o o t t i i n n g g
Correct, replace wiring.
Check opera on
See diagram #1 below
Correct, replace wiring.
Check opera on
See diagram #2 below
Replace motor.
Check opera on
DIAGRAM #2
FTH: VS Serial Port Motors
75