Setup Proflame; Initialize The Control System; Reset The System For Manual Operation; Automatic Safety Restart - kozy heat ROOSEVELT 29 BAK Installation And Operation Manual

Direct vent gas fireplace insert
Table of Contents

Advertisement

11.1 Setup Proflame 2 IFC Module
1.
Locate the control module access switch on the left side of the
fireplace.
2.
Set the main ON/OFF rocker switch in the OFF position.
3.
Install (3) AAA batteries (included in the components packet) in
the remote control battery bay, located at the base of the remote.
4.
Connect the IFC Module to an AC power supply.

11.2 Initialize the Control System

IMPORTANT: Remove all packaging and combustible material from the
firebox before initializing the control system.
NOTE: Performing the next steps will initiate pilot start-up in manual
mode, where the pilot igniter will spark repeatedly. The pilot will ignite
if gas is supplied to the fireplace.
1.
Locate the remote sync button on the control module access
switch on the left side of the fireplace.
2.
Press the remote sync button. The IFC module will BEEP (3) times
and illuminate an amber LED. This indicates the receiver is ready
to synchronize with the transmitter.
3.
Within (5) seconds, push the ON/OFF button on the remote
control. The receiver will BEEP (4) times to indicate the transmitter's
command is accepted, and is set to the transmitter's particular
code. The pilot will automatically ignite.
4.
Press the remote control ON/OFF button again. The pilot will
extinguish, confirming the remote control command. The control
system is now initialized.
5.
Set the main ON/OFF rocker switch to ON position for remote
control operation of the main burner and fireplace features.
POWER SWITCH
REMOTE SYNC BUTTON
BACKUP 9V DC POWER JACK
Figure 11.1, Control module access switch
11.3 Reset the System for
Manual Operation
1.
Set the ON/OFF rocker switch to OFF position.
2.
Press the remote sync button on the IFC module until it emits (3)
beeps and an amber LED is illuminated.
3.
Within (5) seconds, press the remote sync button again. This
will close synchronization with the remote control. The pilot will
automatically light.
Turn the main burner ON by setting the ON/OFF switch in ON
position. The main burner will only operate on HI.
Turn the main burner OFF by setting the ON/OFF switch in the
OFF position. The pilot will remain lit even if burner is turned off,
provided CPI mode is turned on.
32
OPERATING INSTRUCTIONS

11.4 Automatic Safety Restart

This system will execute an automatic turn OFF command for
approximately (5) seconds within (24) hours of a continued pilot
flame ignition to perform a safety check. This allows the system to
verify correct safety functions.
After the turn OFF sequence is completed, the IFC module will re-
execute the latest command.

11.5 Backup Battery Operation

This electronic ignition system utilizes the supplied 110 VAC power
when it is available for all functions of this system. If the AC power is
interrupted during a power outage, plug in the battery pack (9V DC
max, supplied with this fireplace) to the backup 9V DC power jack.
During the power outage, the appliance burner and flame height
adjustment will function. The fan and accent light kit will not function.
See the figure below on how to plug in the battery backup into the
inlet port.
Figure 11.2, Backup Battery and Inlet Port
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
#RVT-29-BAK R.3 November 2019