1.0

Approved Applications Compliance Guide

1.1

Listings and Approvals

1. 1 . 1

Fire

UL
Underwriters Laboratories lists the D7212G Control/Communicator as a Control Unit for Household Fire Warning.
CSFM
Approval by the California State Fire Marshal for Household Fire Warning is pending.
1. 1 .2

Burglary

UL
Underwriters Laboratories lists the D7212G Control/Communicator for:
Central Station, Local, Police Connect, Bank Safe and Vault, Mercantile Safe and Vault, and Grade A Household Systems.
1.2

Introduction

Table 1 on page 7 references components evaluated and listed by Underwriters Laboratories for compatibility with the
control/communicator. These components meet the basic system requirements for the applicable standard.
Section 3.0 System Wiring Diagrams, Issue A beginning on page 9 shows the relationship between the panel and the accessory
components referred to in Table 1 on page 7.
1.3

Optional Compatible Equipment

UL Listed components that do not require evaluation for electrical compatibility can be used in many applications when
installed according to the manufacturer's instructions.
1.3. 1

Burglary Applications

UL Listed burglary alarm sensors that do not require evaluation for electrical compatibility can be used in burglary
applications. In some cases a UL Listed Bosch Security Systems interface module must be used in conjunction with the
sensors. Consult the individual component specification and installation documents to determine suitability.
Test weekly: UL Standard 1023 requires a weekly test for residential burglary applications.
1.3.2

Bank Safe and Vault Applications

The UL Listed Model 5110 Bell and Model 4001-42 External Line Balancer (both made by Rothenbuhler) must be used for
the bell and balanced line module in bank safe and vault applications. Modifications must be made to the Bosch Security
Systems D8108A enclosure to meet UL Standard 681. See the 9000/9000G Series Technogram: UL Certificated Bank Safe and
Vault Applications (P/N: 73-07302-000).
Test bell at arming: UL Standard 365 requires a bell test at arming for bank safe and vault applications.
1.3.3

Fire Applications

UL Listed fire initiating devices not requiring electrical compatibility evaluation can be used in any application. For example:
4-wire smoke detectors, heat detectors, water flow switches, and manual pull stations are suitable fire initiating devices.
Consult the individual component specification and installation documents to determine suitability.
Two-wire smoke detectors only connect to the panel through the D125B Powered Loop Interface so that an earth ground will
not cause an alarm. Two-wire detectors must be evaluated for electrical compatibility, and must be UL Listed for use with the
panel. See the 9000/9000G Series Technogram: Smoke Detector Compatibility (P/N: 33284), or contact the detector
manufacturer.
Other initiating devices, including four-wire smoke detectors connect to the panel through the D129 Dual Class A Initiation
Circuit Module, the D125B Powered Loop Interface, D8127 or D9127 POPITs, or on-board points. When using 4-wire
smoke detectors, install a suitable power supervision unit according to the manufacturer's instructions. Use the D130 Relay
Module, D8129 OctoRelay, or Terminal 8, Switched Aux Power to provide reset capability. See Section 9.0 Off-board Relays of
the D7212G Operation and Installation Guide (P/N: 4998138544) for details on the installation of the D8129.
© 2003 Bosch Security Systems
Approved Applications Compliance Guide
D7212G Approved Applications Compliance Guide