Code
Display text
Description
DP020
Postrun
Post run time of the DHW
DHW
pump/3 way valve after
pump/3wv
DHW production
DP140
DHW load
DHW load type (0 : Combi,
type
1 : Solo)
GP010
GPS Check
Gas Pressure Switch
check on/off
GP017
Max power
Maximum power percent
age in kilo Watt
GP021
Temp diff
Modulate back when delta
Modulating
temperature is larger than
this threshold
GP022
Tfa Filter
Tau factor for average flow
Tau
temperature calculation
GP042
Fan RPM
Maximum fan speed
Max
GP050
Power Min
Minimum power in kilo
Watt for RT2012 calcula
tion
PP007
Min anti-cy
Minimum heat generator
cle time
holding time that can be
reached after a stop
PP012
Stabilization
Stabilization time after
time
heat generator start for
central heating
6.3.3
SCB-01 expansion PCB parameters
Tab.50
Navigation for installer level
Level
Menu path
Installer
General
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
7734325 - v.07 - 22092022
> Installation Setup > SCB-01 > Submenu
Adjustment range
Subme
nu
0 - 99 Sec
Gas
fired ap
pliance
0 = Combi
Gas
1 = Solo
fired ap
pliance
0 = No
Gas
1 = Yes
fired ap
pliance
0 - 1000 kW
Gas
fired ap
pliance
5 - 40 °C
Gas
fired ap
pliance
0 - 255
Gas
fired ap
pliance
0 - 65535 Rpm
GVC
Pneu
matic
0 - 300 kW
Gas
fired ap
pliance
1 - 20 Min
Gas
fired ap
pliance
0 - 180 Sec
Gas
fired ap
pliance
All tables show the factory setting for the parameters.
Important
The tables also list parameters that are only applicable if the boiler
is combined with other equipment.
> Parameters, counters, signals > Parameters >
(1)
570
710
860
1000 1150 1300
10
10
10
10
1
1
1
1
1
1
1
1
294.
352.
414.
495.
2
9
5
8
25
25
25
25
10
10
10
10
5700 5800 3700 4000 4500 4300
80
91
128
127
3
3
3
3
30
30
30
30
6 Settings
10
10
1
1
1
1
565.
642
6
25
25
10
10
153
170
3
3
30
30
43