Installation And Application Information - Daikin Clima-Flex CLIC Series Installation, Operation And Maintenance Manual

Air-cooled scroll compressor chiller water generator unit, refrigerant hfc-410a or 454b 50/60 hz
Hide thumbs Also See for Clima-Flex CLIC Series:
Table of Contents

Advertisement

OPERATING AND STANDBY LIMITS
Table unit CLIC
Table 1.
Maximum standby ambient temperature
Maximum operating ambient temperature
Minimum operating ambient temperature (standard control)
Outgoing chilled water temperature
Outgoing chilled fluid temperatures (with antifreeze) - Note that in cases of high ambient tempera-
ture, the lowest outgoing water temperature settings may be outside the chiller's operating enve-
lope; see the chiller's operating envelope. Outgoing water temperature settings may be outside the
chiller's operating envelope; refer to the Clima Flex Tools to make sure that the chiller is capable of
the required elevation.
Maximum evaporator inlet fluid temperature
Maximum non-operating evaporator inlet fluid temperature
NAMEPLATES
The unit nameplate is located on the outside of the unit power panel. Both the model number and serial number are located on the unit
nameplates; the serial number is unique to the unit.
These numbers should be used to identify the unit in case of service, parts or warranty questions. This nameplate also contains the
unit's refrigerant charge and electrical ratings. The evaporator nameplate is under the insulation and contains the serial number. The
compressor nameplate is located on each compressor and provides pertinent electrical information.
Installation should be performed by qualified personnel who are familiar with local codes and regulations.
INSPECTION
Check all items carefully against the bill of lading. Inspect all units for damage upon arrival. Report shipping damage and file a claim with
the carrier. Check the unit nameplate before unloading, making sure it matches the available power supply.
Clima Flex is not responsible for physical damage that occurs after the unit leaves the factory.
HANDLING
Take care to avoid rough handling of the unit. Do not push or pull the unit from other than the base while seated on properly sized dollies.
To lift the unit, 2-1/2 (64 mm) diameter lifting eyes are provided at the base of the unit. Arrange the spreader bars and cables to prevent
damage to the condenser coils or cabinet (see Figure 1).
All lifting locations must be used to avoid damage to the unit.
Improper rigging, lifting or moving of a unit can result in property damage, serious personal injury or death. Follow the rigging and
moving instructions carefully. Do not stand under the unit while it is being lifted or installed.
iom-clic-cf-eng

Installation and Application Information

!
!
WARNING
!
!
CAUTION
!
!
DANGER
8
130°F (54°C)
113°F (45°C)
55°F(12°)
40°F to 65°F (4°C to 18°C)
15°F to 65°F (-9°C to
18°C)
81°F (27°C)
100°F (38°C)
www.clima-flex.com