Daikin Clima-Flex CLIC Series Installation, Operation And Maintenance Manual page 95

Air-cooled scroll compressor chiller water generator unit, refrigerant hfc-410a or 454b 50/60 hz
Hide thumbs Also See for Clima-Flex CLIC Series:
Table of Contents

Advertisement

Mother /Son Logic
E74
Liquid Press Fault
E75
Main Water Iny Temp Fault
E76
Main Water Ret Temp Fault
W70
Ovld Comp Relay Warning
W71
Overload Compressor Warrnig
W72
Detector Gas Sensor Alarm
W73
DGS High Level Alarm
W74
DGS Modbus Fault
FA1
Fan 1 Inv Alarm
FA2
Fan 2 Inv Alarm
Evaporator Pump control: After the chiller has been started the PumpRequest flag send the signal to Twin Pumps components and it
starts the Pump. In this sequence the Flow switch is monitored and if 5 second after the pump is started and the flow switch is not closed
the Evaporator flow Switch Alarm appears.
When the unit stops, the pump will remain running for 20 seconds.
www.clima-flex.com
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Figure 57. Logic of Flow Switch validation
Figure 58. Logic of Pump control
95